90% GAS FURNACE - ORIFICE SELECTION CHART - NATURAL GAS

CAUTION: Selection of the correct Natural Gas Orifice requires the following information for the specific installation:

1)Altitude in of the installation (ft.).

2)Average energy content of the Natural Gas fuel from the local supplier (BTU/cu. ft.).

For detailed information and instructions for Orifice selection, see the Gas Furnace LP Conversion Kit Index 92-21519-59 and the latest edition of the National Fuel Gas Code Handbook, or the National Standard of Canada, Natural Gas and Propane Installation Code, CAN B149.1.

CAUTION: This information is provided for replacement purposes only. Conversion for operation at High Altitude must be done using the kit specified on the product specification sheet for the unit.

Manual backgroundNOTE: This Orifice sizing chart is based on 15,000 BTU/HR per burner.

Manual backgroundNOTE: Factory installed orifices are calculated and sized based on a Natural Gas heating value of 1075 BTU/cu. ft. and an elevation of 0 - 2000 ft.

 

 

 

 

Elevation (ft.)

 

 

 

Energy Value

0 - 1999

2000 - 2999

3000 - 3999

4000 - 4999

5000 - 5999

6000 - 6999

7000 - 7999

8000 - 8999

(BTU/cu. ft.)

 

 

 

 

 

 

 

 

850

62-22175-47

62-22175-48

62-22175-48

62-22175-49

62-22175-49

62-22175-49

62-22175-50

62-22175-50

900

62-22175-48

62-22175-49

62-22175-49

62-22175-49

62-22175-50

62-22175-50

62-22175-50

62-22175-51

975

62-22175-49

62-22175-50

62-22175-50

62-22175-50

62-22175-51

62-22175-51

62-22175-51

62-22175-52

1075

62-22175-50

62-22175-51

62-22175-51

62-22175-51

62-22175-51

62-22175-52

62-22175-52

62-22175-52

1170

62-22175-51

62-22175-51

62-22175-52

62-22175-52

62-22175-52

62-22175-53

62-22175-53

62-22175-53

90% GAS FURNACE - ORIFICE SELECTION CHART - LP

CAUTION: Selection of the correct LP Orifice requires the altitude of the specific installation (ft.).

For detailed information and instructions for Orifice selection, see the Gas Furnace LP Conversion Kit Index 92-21519-59 and the latest edition of the National Fuel Gas Code Handbook (NFG), or the National Standard of Canada, Natural Gas and Propane Installation Code, CAN B149.1.

CAUTION: This information is provided for replacement purposes only. Conversion to LP or for operation at High Altitude should be done using the kit(s) specified on the product specification sheet for the unit.

NOTE: This Orifice sizing chart is based on 15,000 BTU/HR per burner. Also, the chart is developed using the specified pressure setting of 10 in. water column instead of the 11.0 in water column used by the NFG and CANB149.1.

Manual backgroundNOTE: Orifices supplied in the LP Conversion Kit are calculated and sized based on an altitude of 0 - 2000 ft.

Elevation (ft.)

Orifice

0 to 2000 ft.

62-22175-91

2001 to 3000

62-22175-91

3001 to 4000

62-22175-90

4001 to 5000

62-22175-58

5001 to 6000

62-22175-59

6001 to 7000

62-22175-60

7001 to 8000

62-22175-62

8001 to 9000

62-22175-63

9001 to 1000

62-22175-64

15-February-2012

92-42810-GLDH

Page 11 of 16

Page 11
Image 11