Heat Controller BHD-301-C, BHD-501-B, BHD-651-C Troubleshooting Guide, Condition, Cause, Remedy

Models: BHD-651-C BHD-501-B BHD-301-C

1 27
Download 27 pages 31.56 Kb
Page 17
Image 17

4. TROUBLESHOOTING GUIDE

CONDITION

CAUSE

REMEDY

1. Dehumidifier does not start. (Both

No power

Check power supply at outlet.

compressor and fan motor do not

 

Correct if none.

operate.)

 

 

Poor plug contact at outlet.

Install plug properly or replace it.

 

 

 

 

 

Bucket is full.

If Auto Shut Off lights, empty the bucket

 

 

and replace properly.

 

 

 

 

Humidity control is at Off position

Turn the humidity control switch toward

 

 

Max.

 

 

 

 

Wire disconnected or loose

Connect wire. Refer to wiring diagram for

 

 

terminal identification. Repair or replace

 

 

loose terminal.

 

 

 

 

Capacitor.

Test capacitor.

 

(Discharge capacitor before testing.)

Replace if not within ±10% of

 

 

manufacturer's rating. Replace if shorted,

 

 

open, or damaged.

 

 

 

2. Motor runs but compressor does not

Voltage (115V ± 10%)

It must be between 103.5V and 126.5V. If

run.

 

not within limits, call an electrician

 

 

 

 

Wiring

Check the wire connections; If loose,

 

 

repair or replace the terminal. If the wires

 

 

are disconnected, refer to wiring diagram

 

 

for identification, and replace the wires.

 

 

Check the wire connections; If not

 

 

according to the wiring diagram, correct

 

 

the connections.

 

 

 

 

Rotary switch

Check for continuity, refer to the wiring

 

 

diagram for terminal identification. Replace

 

 

the switch if the circuit is open.

 

 

 

 

Defrost control

The Defrost Control senses frost build-up

 

 

on the evaporator coil and automatically

 

 

shuts off the compressor. The fan

 

 

continues to run, drawing air across the

 

 

coil, and melting the frost. When the coil is

 

 

defrosted, the compressor automatically

 

 

restarts, and dehumidifying resumes.

 

 

 

 

Capacitor

Check the capacitor.

 

(Discharge capacitor before servicing.)

Replace if not within ±10% of

 

 

manufacturer's rating. Replace if shorted,

 

 

open, or damaged.

 

 

 

 

Compressor

Check the compressor for open circuit or

 

 

ground. If open or grounded, replace the

 

 

compressor.

 

 

 

 

Overload protector (OLP)

Check the compressor OLP if externally

 

 

mounted. Replace if open. (If the

 

 

compressor temperature is high, remove

 

 

OLP, cool, and retest.)

 

 

 

3. Does not defrost control.

Defrost control is defective.

Check defrost control, replace it.

 

 

 

4. Insufficient dehumidification

Low relative humidity

Turn dehumidifier off.

 

Poor air circulation

Move dehumidifier to obtain free and

 

 

unobstructed air circulation.

 

 

 

 

H/E clogged with dust and dirt

Clean evaporator and/or condenser assembly

 

 

 

 

Air filter is dirty.

Clean it.

 

 

 

 

Motor is not operating.

Check Motor, repair or replace it.

 

 

 

— 17—

Page 17
Image 17
Heat Controller BHD-301-C, BHD-501-B, BHD-651-C service manual Troubleshooting Guide, Condition, Cause, Remedy