3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM

1.When replacing a refrigeration component, be sure to discharge the refrigerant system by using a refrigerant recovery system.

2.After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with service valves.

5.After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

6.Evacuate as follows.

1)Connect the vacuum pump, as illustrated in Figure 30A.

2)Start the vacuum pump, slowly open manifold valves A and B two full turns counterclockwise and leave the valves open.

The vacuum pump is now pulling through valves A and B to valve C by means of the manifold and entire system.

CAUTION

If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

3)Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum are obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

4)Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 30B. Open valve C.

Discharge the line at the manifold connection.

5)The system is now ready for final charging.

7.Recharge as follows :

1)Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put

in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

2)Connect the charging cylinder as shown in Figure 30B.

With valve C open, discharge the hose at the manifold connection.

3)Open valve A and allow the proper charge to enter the system. Valve B is still closed.

4)If more charge is required, the high-side will not take it. Close valve A.

5)With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the Low- side.

b.Watch the Low-side gauge; allow pressure to rise to 30 lbs.

c.Turn off valve B and allow pressure to drop.

d.Repeat steps B and C until the balance of the charge is in the system.

6)When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

—15—

Page 15
Image 15
Heat Controller BHD-651-D, BHD-301-D, BHD-501-D service manual HOW to Replace the Refrigeration System

BHD-501-D, BHD-301-D, BHD-651-D specifications

The Heat Controller BHD series, including models BHD-651-D, BHD-301-D, and BHD-501-D, represents a significant advancement in indoor heating technology. Designed for efficiency and user convenience, these units cater to diverse heating needs in residential and commercial spaces.

The BHD-651-D model is notable for its high heating capacity, making it ideal for larger areas. With a robust power output, it ensures quick and consistent warmth even in the coldest conditions. This unit features a sleek design that seamlessly blends into various interior styles, along with advanced insulation materials that maintain heat, minimizing energy consumption.

The BHD-301-D serves as a versatile solution for medium-sized rooms. It boasts a compact design while still providing ample heating power. One of its main features is the adjustable thermostat, which allows users to set their desired temperature with precision. Additionally, this model includes a programmable timer, enabling users to schedule heating in advance for optimized energy use.

Meanwhile, the BHD-501-D strikes a balance between power and size, making it suitable for both residential and smaller commercial settings. It offers innovative climate control features, such as a smart sensor that detects the room’s temperature and adjusts the output accordingly. This model also incorporates a user-friendly control panel, allowing easy access to temperature settings and mode selections.

All three models utilize advanced thermal technologies that enhance operational efficiency. They employ eco-friendly refrigerants, contributing to reduced environmental impact while maintaining excellent heating performance. Energy-saving modes are also integrated into each unit, allowing users to operate the heaters at lower power levels during off-peak hours.

Safety is a key consideration in the design of the BHD series. Each model is equipped with multiple safety features, including overheat protection and tip-over shut-off mechanisms, ensuring safe operation in any environment. The units are designed for noise reduction, enabling quiet operation and maintaining a peaceful atmosphere in the space.

In summary, the Heat Controller BHD series offers a range of features tailored for various heating needs. With their blend of advanced technologies, energy efficiency, and safety measures, the BHD-651-D, BHD-301-D, and BHD-501-D are excellent choices for anyone looking to enhance their indoor heating experience. Whether for a cozy living room or a bustling office, these models provide reliable, effective, and safe heating solutions.