4. TROUBLESHOOTING GUIDE

CONDITION

CAUSE

REMEDY

1. Dehumidifier does not start. (Both

No power

Check power supply at outlet.

compressor and fan motor do not

 

Correct if none.

operate.)

 

 

Poor plug contact at outlet.

Install plug properly or replace it.

 

 

 

 

 

Bucket is full.

If Auto Shut Off lights, empty the bucket

 

 

and replace properly.

 

 

 

 

Humidity control is at Off position

Turn the humidity control switch toward

 

 

Max.

 

 

 

 

Wire disconnected or loose

Connect wire. Refer to wiring diagram for

 

 

terminal identification. Repair or replace

 

 

loose terminal.

 

 

 

 

Capacitor.

Test capacitor.

 

(Discharge capacitor before testing.)

Replace if not within ±10% of

 

 

manufacturer's rating. Replace if shorted,

 

 

open, or damaged.

 

 

 

2. Motor runs but compressor does not

Voltage (115V ± 10%)

It must be between 103.5V and 126.5V. If

run.

 

not within limits, call an electrician

 

 

 

 

Wiring

Check the wire connections; If loose,

 

 

repair or replace the terminal. If the wires

 

 

are disconnected, refer to wiring diagram

 

 

for identification, and replace the wires.

 

 

Check the wire connections; If not

 

 

according to the wiring diagram, correct

 

 

the connections.

 

 

 

 

Rotary switch

Check for continuity, refer to the wiring

 

 

diagram for terminal identification. Replace

 

 

the switch if the circuit is open.

 

 

 

 

Defrost control

The Defrost Control senses frost build-up

 

 

on the evaporator coil and automatically

 

 

shuts off the compressor. The fan

 

 

continues to run, drawing air across the

 

 

coil, and melting the frost. When the coil is

 

 

defrosted, the compressor automatically

 

 

restarts, and dehumidifying resumes.

 

 

 

 

Capacitor

Check the capacitor.

 

(Discharge capacitor before servicing.)

Replace if not within ±10% of

 

 

manufacturer's rating. Replace if shorted,

 

 

open, or damaged.

 

 

 

 

Compressor

Check the compressor for open circuit or

 

 

ground. If open or grounded, replace the

 

 

compressor.

 

 

 

 

Overload protector (OLP)

Check the compressor OLP if externally

 

 

mounted. Replace if open. (If the

 

 

compressor temperature is high, remove

 

 

OLP, cool, and retest.)

 

 

 

3. Does not defrost control.

Defrost control is defective.

Check defrost control, replace it.

 

 

 

4. Insufficient dehumidification

Low relative humidity

Turn dehumidifier off.

 

Poor air circulation

Move dehumidifier to obtain free and

 

 

unobstructed air circulation.

 

 

 

 

H/E clogged with dust and dirt

Clean evaporator and/or condenser assembly

 

 

 

 

Air filter is dirty.

Clean it.

 

 

 

 

Motor is not operating.

Check Motor, repair or replace it.

 

 

 

— 17—

Page 17
Image 17
Heat Controller BHD-501-D, BHD-651-D, BHD-301-D service manual Troubleshooting Guide

BHD-501-D, BHD-301-D, BHD-651-D specifications

The Heat Controller BHD series, including models BHD-651-D, BHD-301-D, and BHD-501-D, represents a significant advancement in indoor heating technology. Designed for efficiency and user convenience, these units cater to diverse heating needs in residential and commercial spaces.

The BHD-651-D model is notable for its high heating capacity, making it ideal for larger areas. With a robust power output, it ensures quick and consistent warmth even in the coldest conditions. This unit features a sleek design that seamlessly blends into various interior styles, along with advanced insulation materials that maintain heat, minimizing energy consumption.

The BHD-301-D serves as a versatile solution for medium-sized rooms. It boasts a compact design while still providing ample heating power. One of its main features is the adjustable thermostat, which allows users to set their desired temperature with precision. Additionally, this model includes a programmable timer, enabling users to schedule heating in advance for optimized energy use.

Meanwhile, the BHD-501-D strikes a balance between power and size, making it suitable for both residential and smaller commercial settings. It offers innovative climate control features, such as a smart sensor that detects the room’s temperature and adjusts the output accordingly. This model also incorporates a user-friendly control panel, allowing easy access to temperature settings and mode selections.

All three models utilize advanced thermal technologies that enhance operational efficiency. They employ eco-friendly refrigerants, contributing to reduced environmental impact while maintaining excellent heating performance. Energy-saving modes are also integrated into each unit, allowing users to operate the heaters at lower power levels during off-peak hours.

Safety is a key consideration in the design of the BHD series. Each model is equipped with multiple safety features, including overheat protection and tip-over shut-off mechanisms, ensuring safe operation in any environment. The units are designed for noise reduction, enabling quiet operation and maintaining a peaceful atmosphere in the space.

In summary, the Heat Controller BHD series offers a range of features tailored for various heating needs. With their blend of advanced technologies, energy efficiency, and safety measures, the BHD-651-D, BHD-301-D, and BHD-501-D are excellent choices for anyone looking to enhance their indoor heating experience. Whether for a cozy living room or a bustling office, these models provide reliable, effective, and safe heating solutions.