Configuration Settings
The control can be configured to operate a wide range of options. The options listed below with the * are the factory default settings. If these are acceptable, then the unit does not require any additional configuration and is fully operable. To configure the unit, first
select the configuration feature code setting and then an option code to change from the factory default setting.
To enter configuration feature mode:
1. Press and continue to hold the up and down arrow keys and quickly press the OFF key twice within a two (2) sec-
ond time frame. The display will alternate between displaying the feature code C1 and the option code 0 (factory default set- ting). The lower right dot on the display will flash. To enter the other option codes for C1 (rE and L5) press either the up or down arrow key.
To select a configuration feature code other than C1, press the HEAT key until the desired configuration comes up. To
scroll to a previously viewed configuration codes press the COOL key.
Once you have scrolled to the correct feature, then to select the option code for your desired configuration, press either the up or
down key | to scroll through the options of the selected feature code. |
To exit configuration mode:
1.Press the OFF key. Configuration feature mode will also exit if no keys are pressed for a period of two (2) minutes. Below are the most common configuration settings. Additional codes are present and may be accessed within this menu. Contact the manufacturer for additional information.
Feature | Description | Option | Description |
|
Code | Code |
| ||
|
|
| ||
|
|
|
|
|
|
|
|
|
|
C1 | Interface Usage | 0* | Unit is only controlled by the touchpad behind the door. |
|
|
| rE | Unit is both controlled by a wireless thermostat |
|
|
| and/or the touchpad behind the door. |
| |
|
|
|
| |
|
| L5 | Unit is controlled by a wired thermostat only via |
|
|
| on the low voltage terminals. |
| |
|
|
|
| |
C2 | Fan Operation | Au* | The fan only runs with the call for heating or cooling. |
|
|
| On | The fan runs continuously except in the OFF position. |
|
C4 | Room Indentification first two |
|
|
|
| digits (00 to 99) | Set first two digits of room identification |
| |
C5 | Room Identification last two |
|
|
|
| digits (00 to 99) | Set last two digits of room identification |
| |
C6 | Occupancy | 0* | "No Occupancy" detection devices |
|
|
| 1 | Wired Door Switch and Motion Sensor present |
|
|
| 18 | Enter "No Occupancy" routine 18 hours after last control |
|
|
| selection |
| |
|
|
|
| |
C7 | Motion Sensor Type | 1 | Normally Closed Device |
|
|
| 0* | Normally Open Device |
|
C8 | Cooling Temperature Limiting | Select temperature between 60 and 72 for minimum |
| |
|
| cooling set point |
| |
C9 | Heating Temperature Limiting | Select temperature between 74 and 90 for maximum |
| |
|
| heating set point |
| |
C0 | Reverse Cycle "B" or "O" | 8* | Mating thermostat has a "B" terminal |
|
| selection for thermostat | 0 | Mating thermostat has an "O" terminal |
|
c1 |
|
| Not used |
|
c2 | Wired Unrented Set Back | 0* | Not Active |
|
|
| A | Active |
|
c3 | Unrented Cooling Temperature | Select temperature between 60 and 90 unrented cooling set point | ||
c4 | Unrented Heating Temperature | Select temperature between 60 and 90 unrented heating set point |
| |
CA | Twinned Unit | 0* | Not Twinned |
|
|
| 5 | Twinned (Slave) |
|
Cb | Dehumidification | 0* | Not Active |
|
|
| 1 | Active |
|
|
| U | Active in No occupancy / Unrented State | |
CC | Dehumidistat call for a drop in temperature |
| ||
Cd | English/Metric Temperature | F* | Fahrenheit Scale |
|
|
| C | Celsius Scale |
|
CE | Freeze Protection | 1* | On |
|
|
| 0 | Off |
* Indicates factory default.
17