BEACON CONTROLLER
14
TABLE 3
The initial factory settings for the BEACON MICROPROCESSOR BOARD are indicated on the following
chart.
ELECTRIC DEFROST AIR DEFROST
FACTORY SETTINGS FACTORY SETTINGS
DEFROST CYCLES OR TIME DEFROST CYCLES OR TIME
6 PER DAY/ 2 HRS 6 PER DAY/ 2 HRS
4 PER DAY/ 3 HRS X4 PER DAY/ 3 HRS
2 PER DAY/ 6 HRS 2 PER DAY/ 6 HRS X
1 PER DAY/ 12 HRS 1 PER DAY/ 12 HRS
ELAPSED X RUN TIME ELAPSED X RUN TIME
SUPERHEAT SUPERHEAT
6°F6°F
8°FX8°FX
12°F12°F
DEFROST FAIL-SAFE DEFROST FAIL-SAFE
10 MIN 10 MIN
20 MIN 20 MIN
30 MIN X 30 MIN
40 MIN 40 MIN X
60 MIN 60 MIN
MEDIUM XLOW MEDIUM XLOW
TEST XNORM TEST XNORM
TYPE 1 TYPE 2 TYPE 1 TYPE 2
RESET TIME XNORM RESET TIME XNORM
FORCED DEFROST XNORM FORCED DEFROST XNORM
DEFROST END TEMP DEFROST END TEMP
50°F50°FX
70°FX 70°F
90°F90°F
NOTE: When using the Beacon Smart Controller, the Defrost End Temperature for each Beacon board must
be set at 50° F. It is recommended that the room temperature pot for all the slave units be adjusted to the
maximum temperature 60°F when connected in a master/slave configuration.