Heatcraft Refrigeration Products Air-Cooled Condensing Units manual

Models: Air-Cooled Condensing Units

1 24
Download 24 pages 5.47 Kb
Page 17
Image 17
SEMI-HERMETIC COMPRESSORS

SEMI-HERMETIC COMPRESSORS

Unit Specifications

 

 

 

Connections (ID)

Receiver

 

 

Dimensions

 

Net Wt.

Sound

Model

Fig. ++

Compressor

Liquid

Suction

90% Full

Fan(s)

D (In.)

 

W (In.)

H (In.)

Lbs.

Data dBA

 

 

 

 

 

Lbs.

 

 

 

 

 

 

 

 

BS*005H2

A

HAG-0050

3/8

1/2

6.0

1

28.25

 

23.75

 

17.25

161

66

BS*008H2

A

KAN-0075

3/8

5/8

6.0

1

28.25

 

23.75

 

17.25

180

66

BS*008M2

A

KAE-0075

3/8

5/8

6.0

1

28.25

 

23.75

 

17.25

180

66

BS*010H2

A

KAR-0100

3/8

5/8

6.0

1

28.25

 

23.75

 

17.25

175

66

BS*010M2

A

KAM-0100

3/8

5/8

6.0

1

28.25

 

23.75

 

17.25

178

66

BS*015H2

B

KAG-0150

3/8

7/8

10.0

2

28.25

 

37.75

 

17.25

221

69

BS*020H2

B

ERA-0200

3/8

7/8

10.0

2

28.25

 

37.75

 

17.25

293

69

BS*020M2

B

KAK-0200

3/8

7/8

10.0

2

28.25

 

37.75

 

17.25

189

69

BS*021M2

B

ERC-0200

3/8

7/8

10.0

2

28.25

 

37.75

 

17.25

301

69

BS*029M2

C

ERF-0310

1/2

7/8

16.0

2

28.25

 

37.75

 

19.75

391

69

BS*030H2

D

ERF-0310

1/2

7/8

22.0

1

30.25

 

42.5

 

29.75

385

70

BS*030M2

D

3RA-0310

1/2

7/8

22.0

1

30.25

 

42.5

 

29.75

397

71

BS*040H2

D

NRB-0400

1/2

1-1/8

22.0

1

30.25

 

42.5

 

29.75

460

71

BS*050H2

D

NRA-0500

1/2

1-1/8

22.0

1

30.25

 

42.5

 

29.75

462

71

BS*050M2

D

NRM-0500

1/2

1-1/8

22.0

1

30.25

 

42.5

 

29.75

462

71

BS*010M6

A

KAR-010E

3/8

5/8

5.5

1

28.25

 

23.75

 

17.25

178

67

BS*020M6

B

KAK-020E

3/8

7/8

9.0

2

28.25

 

37.75

 

17.25

189

69

BS*021M6

B

ERC-021E

3/8

7/8

9.0

2

28.25

 

37.75

 

17.25

301

70

BS*030M6

D

ERF-031E

1/2

7/8

20.0

1

30.25

 

42.5

 

29.75

397

71

BS*040M6

D

NRB-040E

1/2

1-1/8

20.0

1

30.25

 

42.5

 

29.75

460

73

BS*010L6

A

KAJ-010E

3/8

5/8

5.5

1

28.25

 

23.75

 

17.25

178

67

BS*015L6

B

KAL-015E

3/8

7/8

9.0

2

28.25

 

37.75

 

17.25

225

69

BS*020L6

B

EAD-020E

3/8

7/8

9.0

2

28.25

 

37.75

 

17.25

291

70

BS*021L6

B

EAV-021E

3/8

7/8

9.0

2

28.25

 

37.75

 

17.25

301

70

BS*027L6

C

3AB-031E

1/2

7/8

14.0

2

28.25

 

37.75

 

19.75

391

71

BS*030L6

C

LAH-032E

1/2

7/8

14.0

2

28.25

 

37.75

 

19.75

357

71

BS*030E6

C

LAC-032E

1/2

7/8

14.0

2

28.25

 

37.75

 

19.75

391

71

BS*040L6

D

NRD-032/040E

1/2

1-1/8

20.0

1

30.25

 

42.5

 

29.75

457

73

*= T for Outdoor, N for Indoor, B for Bohnmizer, S for Beacon II™ ++ = See Dimensional Drawings for details.

= Estimated sound pressure values are 10 feet from the unit. For estimating sound pressure from the unit at different distances, deduct the following from the unit values: 20 feet, deduct 6 dBA for 40 feet, deduct 12 dBA for 80 feet, deduct 18 dBA. This data is typical of “free field” conditions for horizontal air cooled condensing units at the outlet of the discharge air. The actual sound measurements may vary depending on the condensing unit

installation. Factors such as reflecting walls, background noise and mounting conditions may have a significant influence on this data.

17

Page 17
Image 17
Heatcraft Refrigeration Products Air-Cooled Condensing Units manual SEMI-HERMETICCOMPRESSORS Unit Specifications