4
APPLICATION
Here is the ideal unit for refrigerated reach-ins. It mounts to
the top of the refrigerator and discharges cold air against the
back wall. With this air flow pattern, the air is not blasted on
the product but is diffused along the back wall and then
gently drawn across the product as it returns to the unit. Thus
uniform temperatures are maintained throughout the
refrigerator. In addition, door sweating and refrigeration loss
due to door opening is greatly reduced because the air is not
discharged against the doors.
FEATURES
•Textured aluminum cabinet.
•Molded Lexan® fan guard.
•Drain fitting at 45-degree angle so drain can be run through
bottom or back of refrigerator.
•Aluminum hangers automatically space the unit the correct
distance from the back wall.
•Stainless steel screws - prevent rust streaks.
•Room for expansion valve inside unit.
•Knockouts in sides and top plus openings in rear provide
maximum flexibility for electrical connection.
Model CHigh Profile Reach In Unit Cooler•Full collar aluminum fins on expanded copper tubes.
•Internal junction box with pigtail leads for electrical
connection.
•Motors are thermally protected and permanently lubricated.
• UL listed for the United States and Canada; UL classified to
NSF standards.
•Optional corrosion-resistant coated coil available (Model CK)
for optimum protection in corrosive environments.
Performance/Electrical Data
MOTOR DATA CONNECTIONS (INCHES) APPROX.
MODEL BTUH 115/1/60
208-230/1/60
COIL SHIP WT.
C 10˚F TD CFM QTY
TOTAL FLA TOTAL FLA
INLET SUCTION DRAIN (LBS.)
13 1300 235 1 1.0 0.5 1/2FN 3/8ID 1/2OD 16
17 1700 250 1 1.0 0.5 1/2FN 3/8ID 1/2OD 17
23 2300 265 1 1.0 0.5 1/2FN 3/8ID 1/2OD 22
30 3000 480 2 2.0 1.0 1/2FN 1/2ID 1/2OD 27
†43 4300 520 2 2.0 1.0 1/2FN 1/2ID 1/2OD 40
†Size 43 uses external equalized expansion valve.
MODEL DIMENSIONS (INCHES)
C A B C D W
13 125/8123/8117/16 13/8141/4
17 155/8123/8147/16 13/8171/4
23 211/8123/8211/16 7/8223/4
30 261/8123/82513/16 127
3/4
43 365/16 ---- ---- ---- 38
DIMENSIONAL DATA
C (K) 43 B FVintage
A = 115/1/60
B = 208-230/1/60
C = High Profile
Unit Cooler
K = Coated Coil
(Optional)
Size
NOMENCLATURE