5
Motor Heater
Model No. of Amps. Amps.
Size Motors A* B* A* B*
09 1 0.8 0.4 4.1 2.07
12 2 1.6 0.8 5.22 2.61
16 2 1.6 0.8 6.09 .04
21 1 1.0 0.5 9.57 4.78
28 - 1.2 - 5.7
5 2 - 1.0 - 7.0
5 - 1.5 - 8.5
Part 115 Volt 208-230 Volt
Description 09 12 16 21 09 12 16 21 28 35 53
Motor 2500701 2500701 2500701 250201 2500801 2500801 2500801 25001 2500801 25001 25001
Fan Blade 5101B 5101B 5101B 2100201 5101B 5101B 5101B 2100201 5101B 2100201 2100201
Fan Guard 5054D 5054D 5054D H5028 5054D 5054D 5054D H5028 5054D H5028 H5028
Heater 459N 4540N 4541N 4545N 4542N 454N 4544N 4546N H50097 24700701 24700702
Heater Clip 554J 554J 554J 554J 554J 554J 554J 554J H5009 554J 554J
Defrost Control 5709L 5709L 5709L 5709L 5709L 5709L 5709L 5709L 5709L 5709L 5709L
Mount 91179001 91179001 91179001 2101401 91179001 91179001 91179001 2101401 91179001 2101401 2101401
Step “A” - Normal Refrigeration Cycle
1.. Power.is.supplied.to.N.and.4.terminals.by.the.timer.
2.. The.fan.delay.and.defrost.termination.thermostat.is.closed.in.the..
. fan.delay.position.and.open.in.the.defrost.termination.position.
3.. The.defrost.heater.is.o.
4.. The.compressor.operates.in.accordance.with.the.demands.of.the..
. refrigeration.system.temperature.and/or.pressure.controls.
5.. The.unit.cooler.fan.operates.continually.
6.. Frost.builds.up.slowly.on.the.evaporator.
Step “B” - Defrost Cycle
1.. Defrosting.of.the.evaporator.is.started.automatically.by.the.timer..
. at.predetermined.times.-.typical.settings.of.the.timer.would.be.1.to..
. 3.defrost.periods.per.24.hours.
2.. The.timer.mechanically.opens.switch.“A”.which.breaks.the.circuit.to..
. the.compressor.and.evaporator.fan.motors,.thereby.shutting.them..
. o,.and.closes.switch.“B,”.thereby.permitting.current.to.ow.to..
. the.heater.
3.. The.heater.recessed.in.slots,.gives.up.heat.directly.to.the.ns.of.the..
. evaporator...This.heat.raises.coil.and.refrigerant.temperature...
. to.32ºF.causing.the.frost.to.melt.
4.. Frost.on.the.evaporator.is.melted.and.defrost.water.drips.into.the..
. heated.drain.pan.and.ows.down.the.drain.
5.. When.frost.has.completely.melted.from.the.coil,.the.coil.starts.to..
. warm.up.beyond.32ºF.
Step “C” - Coil Re-Cooling Cycle
1.. When.the.coil.warms.up.to.55ºF,.the.defrost.termination.thermostat..
. closes.which.allows.the.current.to.ow.to.the.solenoid.in.the.timer,..
. which.then.energizes.and.trips.the.timer.switch.back.to.its.normal..
. position.(switch.“A”.closed,.switch.“B”.open)..The.fan.delay.portion..
. of.this.thermostat.is.now.open.
2.. The.compressor.now.starts.
3.. Then.fan.motors.remain.o.because.the.fan.delay.thermostat.is..
. open..This.prevents.warm.air.from.being.blown.into.the.. .
. refrigerated.space.
4.. The.evaporator.coil.cools.down.approaching.operating.. .
. temperature..Superheated.gas.only.passes.to.the.compressor.
Step “D” - Return to Normal
Refrigeration Operation
1.. When.the.coil.temperature.reaches.35ºF,.the.fan.control.switch..
. closes...This.allows.current.to.ow.to.the.fan.motor.and.the.unit.is..
. now.back.in.operation.as.in.Step.“A.”
IMPORTANT
1.. On.initial.“pull.down”.of.a.warm.box,.the.fan.will.not.start.until.coil..
. temperature.reaches.approximately.35ºF..If.box.is.still.. .
. comparatively.warm.(60ºF).when.the.fan.starts,.then.blowing.this..
. warm.air.over.the.coil.may.cause.it.to.warm.up.to.55ºF.and.thus..
. stop.the.fan..Therefore,.fan.may.recycle.several.times.on.initial..
. “pull.down.”
2.. The.timer.has.an.adjustable.fail-safe.feature.which.will.return.the..
. system.to.the.refrigeration.cycle.at.the.end.of.a.predetermined..
. time.(factory.set.at.24.minutes).if.automatic.control.devices.fail.
3.. Frequent.defrost.periods.are.not.necessary!.The.determining.factor..
. for.number.of.defrosts.per.day.is.the.frost.load..When.frost.“build-.
. up”.results.in.a.loss.of.refrigeration.capacity,.then.a.defrost.is...
. required...One.to.three.defrosts.per.day.are.recommended.
4.. A.low.temperature.thermostatic.expansion.valve.with.pressure..
. limiting.feature.is.desirable.for.use.with.these.units..Such.a.valve..
. prevents.feeding.of.refrigerant.to.the.coil.during.the.defrost.cycle.
Sequence of OperationTypical Wiring Diagram for Thin Profile Electric Defrost Unit Cooler1.. Use.copper.conductors.only.
2.. Unit.must.be.grounded.
3.. Timer-Paragon.Model.8145-20.may.be.factory.supplied,
. eld.installed,.or.eld.supplied.and.installed.
4.. Fan.delay.and.defrost.termination.-.Red.to.N,.Brown.to.X,
. Black.to.F...Fans.will.not.operate.until.thermostat.resets.
5.. Heater.limit:..Red.to.N,.White.to.H.omitted.on.model.28;
. heater.is.connected.directly.to.N.
6.. *Indicates.electrical.code:.A=115/60/1,.B=208-230/60/1.
Commercial Refrigeration Parts