11
Standard or Connections (In.) Approx.
Reverse Flow Dimensions (In.) Coil Shipping
Models H L M W Inlet Suction Drain Wt. (Lbs.)
1 17 /4 16 7/8 12 1/4 15 5/8 /8 OD /8 OD 5/8 OD 19
17 19 /4 16 7/8 14 1/4 15 5/8 /8 OD /8 OD 5/8 OD 20
2 19 /4 2 1/4 14 1/4 22 /8 OD 1/2 OD 5/8 OD 28
Mounting
The.standard. ow. mullion. unit. draws. air. in. at. the. top. and.
discharges.out.the.bottom..The.reverse.ow.mullion. draws.air.
in.at.the.bottom.and.discharges. out.the.top...The.unit.may.be.
mounted.in.a.mullion.or.against.a.back.or.side.wall.
When.mounting.to.the.mullion.of.under. counter.refrigerators,.
mounting.holes.are.located.on.both.ends.of.the.unit.for.attaching.
to.“customer.furnished”.mounting.brackets.
When.wall.mounted,.four.“L”.type.brackets.and.eight. stainless.
steel.sheet.metal.screws.are.provided.to.attach.the.brackets.to.
side.panels.
IMPORTANT: A minimum of 2 inches must be provided
between the top of the unit and the top of the cabinet.
Standard & Reverse Air Flow Wall Mullion Unit CoolerDimensional Data
25°F Sat. Suction Temp. 20°F Sat. Suction Temp.
Model BTUH @ R-22 BTUH @ R-22
Size 10°F TD Alco Sporlan 15°F TD Alco Sporlan
1 100 1950
17 1700 HFS-1/4HC EFV-1/5C 2550 HFS-1/4HC
2 200 450
Expansion Valve Recommendations
Part Standard Reverse
Description Down Flow Up Flow
115V Motor 2500701 2500701
208/20V Motor 2500801 2500801
Fan Blade 5102C 5117C
Fan Guard (1-17) 5076E 5076E
Fan Guard (2) 5077E 5077E
Motor Mount 91179001 91179001
Drain Pan (1-17) 74422002 74422002
Drain Pan (2) 7446002 7446002
FOR FOOD
SERVICE
INSTALLATIONS
. . . seal any joint
between unit cooler and
cooler liner with a sealant
listed by the National
Sanitation Foundation,
Standard 51
A.top.barrier.is.supplied.and.must.be.used.if.combustible.material..
is.above.the.unit..On.reverse.ow.models.the.barrier.may.be.used.
to.direct.the.air.straight.out.or.up.at.a.45°.angle..Holes.and.slots.
are.provided.to.adjust.the.barrier..If.noncombustible.material.is.
used.above.the.unit,.the.barrier.may.be.discarded.if.desired.
Knockouts.are.provided.for.bringing.the.refrigerant.piping.through.
either.end.of.the.cabinet..An.electrical.knockout.is.provided.into.
an.internal.junction.box.
Dimensional Diagram
NOMENCLATURE
XXX K 13 A G
KM = Standard Vintage
Air Flow
RAM=
Reverse
Air Flow A = 115-1-60
K =
Coated Coil
B = 208/20-1-60
Size
EFV-1/C
EFV-1/5C
Replacement Parts