15
PROGRAMMING AND REVIEWING SETTINGS/CHANGES (contd.)
Use this button to CLEAR/TEST
Pressing this button ONCE will return the LED display to the default
display. With the system in the
OFF
mode, pressing and holding
this button will start the TEST mode. In the TEST mode it will
cycle through each output for 10 seconds. The display will only
show tst during TEST mode. Test mode will automatically
terminate after 3 sequences.
STATUS INDICATOR LED
A RED, three-digit , alphanumeric LED on the Beacon II board indicates status, alarms and
error codes.
LED Display
OFF Box Temp /
oFF
Box Temperature/ Mode is displayed
All Evaporators
COOLING

Single Evaporator

- Box Temp /
Coo
Box Temperature/ Mode is displayed

Multiple Evaporators

Master Evap - Box Temp /
Coo
Box Temperature/ Mode is displayed
Slave Evaps -
Coo
Operating Mode is displayed
Pumpdown
All Evaporators
Pdn
DEFROST
All Evaporators
dEF
TEST
All Evaporators
tSt
SERVICE
All Evaporators
SEr
ALARMS
A 1
High Box Temp
A 2
Low Box temp
A 3
System Start-up failure
Compressor pumps down and tries to
restart after 4 minutes.
A 4
Input Fault
Box Temp., Suction Temp., Pressure
Transducer open or not installed
Programming & Reviewing
LOCKING THE BEACON II BOARD
The Beacon II board is lockable to prevent programmed setting changes by unauthorized
personnel. When locked, the program setpoints cannot be changed.
To lock the setting:
Press PROGRAM REVIEW button.
Press and hold MONITOR button.
While holding MONITOR button, press ENTER button.
The LCD will display Loc.
This will prevent unauthorized personnel program changes. To unlock, repeat steps above.
LCD will display UnL.