25
PROBLEM Step ACTION ITEM IF OK IF NOT OK
1. Check wiring connection to the board Correct field wiring to the board
2. Low Pressure Safety (LPS) Tripped:
Check for correct refrigerant type Change setpoint to match refrigerant
Check refrigerant charge Add more refrigerant to proper charge
Check LPS setting Correct LPS setting
Check LPS wiring Correct LSP wiring
Check EEV operation (stuck?) Clean or replace EEV
Check coil for icing Defrost coil (see
E6
, step 2)
Check for correct superheat reading Check/replace sensor or transducer
Check for correct nozzle selection Replace distributor nozzle
Check for clogged EEV inlet screen Replace EEV
Check line sizing Correct line sizing
Check LPS time delay relay setting Reset to 1 minute
Check operation of LPS Replace Low Pressure Safety Switch
3. High Pressure Safety (HPS) Tripped:
Check for system overcharge Reclaim/recover excess charge
Check for non-condensables Remove all non-condensables
Check condenser fan motor and blade Repair or replace motor and/or blade
Check for dirty condenser coil Clean condenser coil
Check head pressure controls Adjust or replace faulty controls
Check fan cycling controls Adjust or replace faulty controls
Check liquid line sizing Correct line sizing
Check for liquid line restrictions Repair line or remove restrictions
Check operation of HPS Replace HPS if necessary
E7
Compressor 4. Oil Pressure Safety (OPS) Tripped:
Shutdown Check oil level in compressor Add oil to crankcase to minimum level
Check oil sump screen pickup Clean or replace pickup screen
Check oil pump pressure Replace compressor oil pump
Check for proper piping practices Go to Correct piping to minimize oil logging
Check for low superheat (see
E6
) next step Correct per steps in
E6
Check operation of auxiliary relay (R6) Replace auxiliary relay
Check OPS sensor Replace faulty OPS sensor
Check operation of OPS Replace faulty OPS
5. Compressor Module Tripped (when supplied):
Check module Replace faulty module
Check superheat at compressor inlet Reduce superheat (TXV adjust, etc.)
Check compressor for overheating Correct overheating problem
Check suction pressure (too low?) Consider crankcase pressure regulator or
other measures
6. Phase Loss Monitor (PLM) Tripped:
Check presence of all phase legs Correct power phase problem
Check power supply Correct power supply problems
Check operation of PLM Replace faulty PLM
7. Demand Cooling (when supplied):
Check auxiliary relay Replace auxiliary relay
Check demand cooling device Replace faulty demand cooling device
8. Check compressor relay on board Replace board if relay is faulty
Beacon II Troubleshooting Guide (continued)