Heatcraft Refrigeration Products VA Model TL, Thin Profile Electric Defrost Reach-InUnit Cooler

Models: U KMK C BBL RAMK BBM VA BTO TL TA

1 12
Download 12 pages 50.55 Kb
Page 4
Image 4
Model TL

Model TL

Thin Profile Electric Defrost Reach-In Unit Cooler

Features

Electric defrost insures positive heat source

Built-in fan delay allows coil to be chilled before returning to the normal cooling cycle

Defrost terminates on coil temperature eliminating excessive defrost period

Textured aluminum cabinet

Molded Lexan® guard

Knockouts provided on sides for electrical connections - opening in rear for coil connections

Stainless steel screws

Motors are thermally protected and permanently lubricated

Internal junction box for electrical connection

Plate type aluminum fins with full collars on expanded copper tubes

Coils are dehydrated and sealed

Easy to install and maintain

All models UL listed for the US and Canada

UL classified to NSF standards

Sweat inlet connection to reduce leaks

(flare connection available as a ship loose option)

Application

Model TL low temperature unit cooler has a completely automaticdefrostsystem. Mountedinthetopofarefrigerator,its extremelycompactcabinetmakesitpossibletoutilizetheentire top shelf area for storage. Having a normal operating range of 15°F to -20°F, this unit is ideally suited for such applications as commercial freezers, ice cream boxes and bakery freezers.

Nomenclature

 

 

 

TL

12 B G

Thin Profile

 

 

 

 

 

 

 

 

 

 

 

 

 

Vintage

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric Defrost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A = 115/1/60

 

 

 

 

 

 

 

 

 

 

B = 208-230/1/60

 

 

 

 

 

 

 

 

 

 

Table 3. Performance and Electrical Data

 

BTUH 10˚F TD

 

 

Motor Data

 

 

Heater Data

Connections (in.)

Approx.

Model

20˚F

-10˚F

CFM

Qty.

115/1/60

208-230/1/60

Watts

115/1/60

208-230/1/60

Coil Inlet

Suction

Drain

Ship Wt.

 

SST

SST

 

 

Total FLA

 

Total FLA

 

Amps

Amps

OD

ID

OD

(lbs.)

TL09

1,050

900

110

1

0.8

 

0.4

475

4.1

2.1

3/8

3/8

1/2

14

TL12

1,380

1,200

210

2

1.6

 

0.8

600

5.2

2.6

3/8

1/2

1/2

19

TL16

1,780

1,600

210

2

1.6

 

0.8

700

6.1

3.0

3/8

1/2

1/2

23

TL21

2,400

2,100

240

1

1.0

 

0.5

1,100

9.6

4.8

3/8

1/2

1/2

24

TL28

3,200

2,800

335

3

-

 

1.2

1,430

-

5.7

3/8

1/2

1/2

27

TL35*

4,000

3,500

420

2

-

 

1.0

1,600

-

7.0

1/2

5/8

1/2

38

TL53*

6,100

5,300

595

3

-

 

1.5

1,950

-

8.5

1/2

7/8

1/2

53

* Models 35 and 53 use external equalized expansion valves

Table 4. Physical Data

Model

 

 

 

 

 

 

Dimensions (in.)

 

 

 

 

 

 

A

B

C

D

E

F

 

H

J

 

K

L

M

N

P

W

 

 

 

TL09

14-5/8

14

15/16

13-1/2

10-1/2

11-3/8

 

4-1/2

8-7/8

2-1/2

15/16

4-3/8

-

1

16-1/2

TL12

18-5/8

14

15/16

13-1/2

10-1/8

10-1/4

 

4-1/2

8-3/8

9-1/2

15/16

4-3/8

-

1

20-1/2

TL16

22-1/8

15

15/16

14-1/2

11-1/8

12

 

4-1/2

9-3/8

 

11-1/4

15/16

4-3/8

-

1

24

TL21

22-1/8

16-1/2

15/16

16-1/2

14-1/2

18-7/8

 

6-3/4

11-7/8

 

17-1/4

15/16

4-3/8

-

1-1/2

24

TL28

29-3/4

15

15/16

14-1/2

13

20-3/4

 

6-3/4

9-3/4

9-7/8

15/16

4-3/8

-

1

31-5/8

TL35

35-3/4

16-1/2

15/16

16-1/2

14-1/2

33-1/4

 

6-3/4

11-5/8

 

18-3/8

15/16

6

5-1/8

1-1/2

38-3/8

TL53

46-1/2

16-1/2

1-1/8

16-1/2

14-1/2

44

 

6-3/4

11-5/8

30-3/8

1-1/2

6

5-1/8

1-1/2

49-1/8

Diagram 2. Dimensions



Page 4