Herrmidifier Co 6000 Key Features, Adjustable Setpoints, Faults, Conductivity, Average Life

Models: 6000

1 24
Download 24 pages 7.48 Kb
Page 5
Image 5
Key Features

Key Features

Adjustable Setpoints

Capacity

• Range = 50-100%

• Preset at 100% for 6000-1,3,4 Preset at 50% for 6000-2

Low Drain Threshold

• Range = 50-100%

• Preset at 90%

Cycle Time

• Range = 60-300 seconds

• Preset at 60 seconds

Faults

Overcurrent

138% of Rated Current

System Shutdown

Fill System

Fill valve open for 6 hours without achieving capacity setpoint or cylinder full

System Shutdown

End of Cylinder Life

6 hours of operation while on cylinder full without achieving capacity setpoint

System Shutdown (See Pg. 14 for Manual Override)

Conductivity*

Average Life**

Micromhos

Expectancy – Hrs.

(approx.)

(approx.)

100

2000

135

1900

170

1800

250

1300

500

800

750

650

1000

500

*If the conductivity of your supply water is less than 100 micromho, consult Herrmidifier for specific circuit board

adjustments and replacement tank information (GT-176-1).

Unit performance may be affected.

Operation on water of less than 60 micromho is not recommended.

**Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.