Display

Function

Standard

Set

Setting

Value

 

 

 

 

A

01

Frequency Source setting

01

 

 

 

00-Potentiometer 01-Terminal O/OI

 

 

 

 

02-Functions F 01 / A 20

 

 

A

02

Run command source setting

01

 

 

 

01-Terminal FW/RV

02-RUN key

 

 

A

03

Base frequency setting

 

50.0

 

A203

Base frequency setting (2. setting)

 

 

A

04

Maximum frequency setting

50.0

 

A204

Maximum frequency setting (2. setting)

 

 

A

11

External frequency setting start point

0

 

A

12

External frequency setting end point

0

 

A

13

External frequency setting start point bias (in %)

0

 

A

14

External frequency setting end point bias (in %)

100

 

A

15

External frequency start pattern setting

01

 

 

 

00-Per A11 and A13

01-0Hz

 

 

A

16

Time constant of the filter for analog inputs

8

 

A

20 –

Multispeed frequency setting

All are

 

A

35

 

 

0.0Hz

 

A

38

Jog frequency setting

 

1.0

 

A

39

Jog stop mode

 

00

 

 

 

00-Freerun 01-Deceleration

 

 

 

 

02-DC brake

 

 

 

A

41

Torque boost selection method

00

 

 

 

00-Manual 01-Automatic

 

 

A241

Torque boost selection method (2. setting)

 

 

A

42

Value of manual torque boost setting

11

 

A242

Value of manual torque boost setting (2. setting)

11

 

A

43

Manual torque boost frequency adjustment (in %)

10.0

 

A243

Manual torque boost frequency adjustment (in %)

 

 

 

 

(2. setting)

 

 

 

A

44

V/F characteristic setting

02

 

 

 

00-Constant torque

 

 

 

 

 

01-Variable torque

02-SLV

 

 

A244

V/F characteristic setting (2. setting)

 

 

A

45

V-Gain setting (in %)

 

100

 

A

51

Selection of DC braking operation

00

 

 

 

00-NO 01- YES

 

 

 

A

52

DC braking frequency setting

0.5

 

A

53

DC braking waiting time setting

0.0

 

A

54

DC braking force setting

0

 

A

55

DC braking time setting

 

0.0

 

A

61

Frequency upper limit setting

0.0

 

A

62

Frequency lower limit setting

0.0

 

A

63,

Jump frequency setting

 

0.0

 

A

65,

 

 

 

 

A

67

 

 

 

 

A

64,

Jump frequency width setting

0.5

 

A

66,

 

 

 

 

A

68

 

 

 

 

A

71

Selection of PID control

 

00

 

 

 

00-NO 01- YES

 

 

 

A

72

P (proportional) gain setting

1.0

 

A

73

I (integral) gain setting

 

1.0

 

A

74

D (differential) gain setting

0.0

 

A

75

Scale conversion of PID control setting

1.00

 

A

76

Feedback signal location setting

00

 

 

 

00-Current 01-Voltage

 

 

A

81

Selection of AVR function

02

 

 

 

00-Available 01-Not available

 

 

 

 

02-Not available at deceleration

 

 

A

82

Selection of voltage of AVR function for the

FE:230/400

 

 

 

motor

 

FE:230/460

 

A

92

Second acceleration time setting

15.0

 

A292

Second acceleration time setting (2. setting)

 

 

A

93

Second deceleration time setting

15.0

 

A293

Second deceleration time setting (2. setting)

 

 

(Table to be continued on next page)

(Continued from previous page)

Display

Function

Standard

Set

Setting

Value

 

 

 

A

94

Selection of method to enable second

00

 

 

 

acceleration/deceleration (acc2/dec2)

 

 

 

 

00-Terminal 2CH 01-A 95 / A 96

 

 

A294

Selection of method to enable second

 

 

 

 

acceleration/deceleration (acc2/dec2)

 

 

 

 

(2. setting)

 

 

A

95

Changed frequency from acc1 to acc2 setting

0.0

 

A295

Changed frequency from acc1 to acc2 setting

 

 

 

 

(2. setting)

 

 

A

96

Changed frequency from dec1 to dec2 setting

0.0

 

A296

Changed frequency from dec1 to dec2 setting

 

 

 

 

(2. setting)

 

 

A

97

Pattern of acceleration setting

00

 

 

 

00-Linear 01-S-curve

 

 

A

98

Pattern of deceleration setting

00

 

 

 

00-Linear 01-S-curve

 

 

Display

Function

Standard

Set

Setting

Value

 

 

b 01

Selection of restart mode

00

 

 

 

00-Alarm 01-0.0Hz restart

 

 

 

 

02-Motor speed match restart

 

 

 

 

03-Motor speed match restart /decel to stop

 

 

b

02

Allowable undervoltage power failure time setting

1.0

 

b

03

Retry waiting time

 

1.0

 

b

12

Level of electronic thermal setting

Rated current

 

b212

Level of electronic thermal setting (2. setting)

of inverter

 

b

13

Selection of electronic thermal characteristic

01

 

 

 

00-Reduced torque 01-Constant torque

 

 

b213 Selection of electronic thermal characteristic

01

 

 

 

(2. setting)

 

 

 

b

21

Selection of overload limit operation mode

01

 

 

 

00-NO 01-Accel & constant speed

 

 

 

 

02-Constant speed

 

 

 

b

22

Level of overload limit setting

Rated current

 

 

 

 

 

times 1.25

 

b

23

Rate of deceleration at overload restriction

1.0

 

b

31

Selection of software lock mode

01

 

 

 

00-Terminal, no change

 

 

 

 

01-Terminal, frequency change

 

 

 

 

02-Keypad, no change

 

 

 

 

03-Keypad, frequency change

 

 

b

81

Analog meter adjustment

80

 

b

82

Start frequency adjustment

0.5

 

b

83

Carrier frequency setting (kHz)

5.0

 

b

84

Initialization will 00-Clear trip history

00

 

 

 

01-Restore data & parameters to factory settings

 

 

b

85

Selection of initialized data

-FE:01 -FU:02

 

b

86

Frequency converted value setting

1.0

 

b

87

STOP key active in terminal mode

00

 

 

 

00-YES 01-NO

 

 

 

b

88

Selection of operation when FRS signal is

00

 

 

 

cancelled

 

 

 

 

 

00-Restart at 0 Hz

01-Restart at motor speed

 

 

b

89

Selection of contents of remote display

01

 

 

 

01-Frequency 02-Current 03-Direction

 

 

 

 

04-PID feedback

05-Input terminal status

 

 

 

 

06-Output terminal status 07-Scaled frequency

 

 

b

90

Rate of use (in %) of the regenerative braking

00

 

 

 

resistor during 100 seconds

 

 

 

 

(00= braking resistor not active)

 

 

b

91

Deceleration mode selection when using the

00

 

 

 

STOP key

 

 

 

 

 

00-Deceleration stop

 

 

 

 

01-Free run stop (FRS)

 

 

b

92

Fan ON/OFF selection

00

 

 

 

00-Fan is always on

 

 

 

 

01-Fan is only on if the inverter/motor

 

 

 

 

is running

 

 

 

Display

 

Function

 

 

Standard

Set

 

 

 

Setting

Value

C

01

Function of input terminal 1

 

 

00

 

 

 

00-FW (Forward run)

01-RV (Reverse run)

 

 

 

 

02-CF1 (Multispeed 1)

03-Multispeed 2

 

 

 

 

04-Multispd. 3 05-Multispd. 4 06-JG (Jogging)

 

 

 

 

07-DB (Ext. DC braking) 08-SET (use 2. setting)

 

 

 

 

09-2CH (2. stage accel/decel)

11-FRS (Free run

 

 

 

 

mode) 12-EXT (Extern. trip)

13-USP-function

 

 

 

 

15-SFT (Software lock) 16-AT (Analog input

 

 

 

 

type) 18-RS (Reset)

19-PTC (only for termi-

 

 

 

 

nal 5) 27-UP (remote control acceleration)

 

 

 

 

28-DWN (remote control deceleration)

 

 

C

02

Function of input terminal 2 (See C 01)

01

 

C

03

Function of input terminal 3 (See C 01)

-FE:02 -FU:16

 

C

04

Function of input terminal 4 (See C 01)

-FE:03 -FU:13

 

C

05

Function of input terminal 5 (See C 01)

-FE:18 -FU:09

 

C

06

Function of input terminal 6 (See C 01)

 

-FE:09 -FU:18

 

C

11 –

Polarity input of terminal 1-6

 

 

00 / C 14 only:

 

C

16

00-Normally open

01-Normally closed

 

-FE:00 -FU:01

 

C

21

Function of output terminal 11

 

 

01

 

 

 

00-RUN-signal 01-FA1 (frequency constant)

 

 

 

 

02-FA2 (Frequency at set point) 03-OL (Over-

 

 

 

 

load) 04-OD (PID deviating)

05-AL (Alarm)

 

 

C

22

Function of output terminal 12 (See C 21)

00

 

C

23

Function of FM terminal

00-Analog frequency

00

 

 

 

01-Analog current

02-Digital frequency

 

 

C

24

Function of alarm terminal (See C 21)

05

 

C

31

Polarity of terminal 11

 

 

 

01

 

 

 

00-Normally open

01-Normally closed

 

 

C

32

Polarity of terminal 12 (See C 31)

01

 

C

33

Polarity of terminal AL0/AL1

 

 

01

 

 

 

00-Normally open

01-Normally closed

 

 

C

41

Level of overload signal setting

 

 

Rated current

 

C

42

Arrival frequency setting for acceleration

0.0

 

C

43

Arrival frequency setting for deceleration

0.0

 

C

44

Level of PID deviation signal setting

3.0

 

C81 Frequency command adjustment (terminal O) C 82 Frequency command adjustment (terminal OI)

C

91 – For further use, do not change.

-

-

C

95

 

 

Display

 

Function

Standard

Set

 

Setting

Value

 

 

 

H 01

Autotuning mode:

00-Autotuning off

00

 

 

01-Autotuning on

02-Autotuning/static

 

 

H

02

Motor data: 00-Standard Hitachi 01-Auto

 

00

 

 

H202

Motor data (2. setting)

 

 

 

H

03

Motor capacity

Depending

H203

Motor capacity (2. setting)

on model

H

04

Number of motor poles

 

4

 

 

H204

Number of motor poles (2. setting)

 

 

 

H

05

Motor constant Kp

20

 

 

H205

Motor constant Kp (2. setting)

 

 

 

H

06

Motor stabilization constant

100

 

 

H206

Motor stabilization constant. (2. setting)

 

 

 

H

20

Motor constant R1

Depending

H220

Motor constant R1 (2. setting)

on model

H

21

Motor constant R2

 

 

 

H221

Motor constant R2 (2. setting)

 

 

 

H

22

Motor constant L

 

 

 

H222

Motor constant L (2. setting)

 

 

 

H

23

Motor constant Io

 

 

 

 

H223

Motor constant Io (2. setting)

 

 

 

H

24

Motor constant J

 

 

 

H224

Motor constant J (2. setting)

 

 

 

H30 Motor constant R1 Autotuning

H230

Motor constant R1

Autotuning (2. setting)

 

 

H 31

Motor constant R2

Autotuning

 

These

H231

Motor constant R2

Autotuning (2. setting)

 

para-

H 32

Motor constant L Autotuning

 

meters

H232

Motor constant L Autotuning (2. setting)

 

must not

 

be

H 33

Motor constant Io Autotuning

 

 

changed!

H233

Motor constant Io Autotuning (2. setting)

 

 

 

H34 Motor constant J Autotuning

H234 Motor constant J Autotuning (2. setting)

6

7

8

Page 4
Image 4
Hitachi SJ100 manual Display Function Standard Set Setting Value, From previous

SJ100 specifications

The Hitachi SJ100 series represents a significant advancement in the field of variable frequency drives (VFDs), designed to enhance energy efficiency and operational reliability in various industrial applications. Compact in design yet powerful, the SJ100 is tailored for a wide range of tasks, making it a versatile addition to any automation system.

One of the standout features of the SJ100 is its superior control technology, which utilizes advanced vector control methods to ensure optimal motor performance. This allows for precise speed and torque control, leading to enhanced responsiveness and reduced energy consumption. The drive is also capable of handling a diverse array of motor types, including induction and permanent magnet motors, making it suitable for numerous industrial sectors.

The SJ100 incorporates a robust set of built-in features designed to simplify installation and operation. With an easy-to-navigate LCD control panel, users can quickly set parameters and monitor performance. Additionally, the drive includes a variety of communication options, such as Modbus and CANopen, facilitating seamless integration into existing control systems. This adaptability ensures that the SJ100 can be utilized in various setups, from simple single-drive configurations to complex multi-drive systems.

Another notable characteristic of the SJ100 is its energy-saving capabilities. With advanced algorithms and optimized motor control, the drive significantly reduces energy consumption under varying load conditions. This feature not only helps decrease operational costs but also contributes to a more sustainable and environmentally friendly approach to industrial processes.

Moreover, the SJ100 series boasts a high degree of reliability thanks to its robust construction and protective features. It includes integrated protection against over-temperature, over-current, and voltage fluctuations, ensuring the drive operates safely in demanding environments. The SJ100 is also designed with a wide operating temperature range, allowing it to perform reliably in extreme conditions.

Additionally, the drive supports a variety of customizable functions, such as programmable logic, acceleration/deceleration control, and multi-function inputs/outputs. These features empower users to tailor the SJ100 to meet specific application requirements, enhancing productivity and operational efficiency.

In summary, the Hitachi SJ100 series stands out as a cutting-edge solution for industrial automation, combining advanced control technologies, energy efficiency, and robust reliability. Its versatility and user-friendly features make it an exceptional choice for a myriad of applications, reinforcing Hitachi's commitment to innovation in the field of industrial drives.