Chapter 8 List of Data Settings
8 - 4
Default
Code Function name Monitored data or setting
_FF _FEF _FUF
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
A041 Torque boost method selection 00 (manual torque boost), 01 (automatic torque boost) 00 ¯ ¯
A241 Torque boost method selection,
2nd motor 00 (manual torque boost), 01 (automatic torque boost) 00 ¯ ¯
A042 Manual torque boost value 0.0 to 20.0 (%) 1.0 { {
A242 Manual torque boost value, 2nd
motor 0.0 to 20.0 (%) 1.0 { {
A342 Manual torque boost value, 3rd
motor 0.0 to 20.0 (%) 1.0 { {
A043 Manual torque boost frequency
adjustment 0.0 to 50.0 (%) 5.0 { {
A243 Manual torque boost frequency
adjustment, 2nd motor 0.0 to 50.0 (%) 5.0 { {
A343 Manual torque boost frequency
adjustment, 3rd motor 0.0 to 50.0 (%) 5.0 { {
4-18
A044 V/F characteristic curve
selection, 1st motor 00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control), 04 (0Hz-range
sensorless vector), 05 (vector with sensor) 00 ¯ ¯
A244 V/F characteristic curve
selection, 2nd motor 00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control), 04 (0Hz-range
sensorless vector) 00 ¯ ¯
A344 V/F characteristic curve
selection, 3rd motor 00(VC), 01(VP) 00 ¯ ¯
4-16
A045 V/f gain setting 20. to 100. (%) 100. { { 4-15
A046 Voltage compensation gain
setting for automatic torque
boost. 1st motor 0. to 255. 100. { {
A246 Voltage compensation gain
setting for automatic torque
boost, 2nd motor 0. to 255. 100. { {
A047 Slippage compensation gain
setting for automatic torque
boost, 1st motor 0. to 255. 100. { {
V/f characteristic
A247 Slippage compensation gain
setting for automatic torque
boost, 2nd motor 0. to 255. 100. { {
4-18
A051 DC braking enable 00 (disabling), 01 (enabling), 02 (set frequency only) 00 ¯ {
A052 DC braking frequency setting 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.50 ¯ {
A053 DC braking wait time 0.0 to 5.0 (s) 0.0 ¯ {
A054 DC braking force during
deceleration 0. to 100. (%) 0. ¯ {
A055 DC braking time for deceleration 0.0 to 60.0 (s) 0.0 ¯ {
A056 DC braking/edge or level
detection for [DB] input 00 (edge operation), 01 (level operation) 01 ¯ {
A057 DC braking force for starting 0. to 100.(%) 0. ¯ {
A058 DC braking time for starting 0.0 to 60.0(s) 0.0 ¯ {
DC braking
A059 DC braking carrier frequency
setting 0.5 to 15.0(kHz) 5.0 ¯ ¯
4-20
A061 Frequency upper limit setting 0.00 or "1st minimum frequency limit" to "maximum frequency" (Hz) 0.00 ¯ {
A261 Frequency upper limit setting,
2nd motor 0.00 or "2nd minimum frequency limit" to "maximum frequency, 2nd motor" (Hz) 0.00 ¯ {
A062 Frequency lower limit setting 0.00 or "start frequency" to "maximum frequency limit"
(Hz) 0.00 ¯ {
A262 Frequency lower limit setting,
2nd motor 0.00 or "start frequency" to "maximum frequency, 2nd motor limit"
(Hz) 0.00 ¯ {
4-24
A063 Jump (center) frequency setting
1 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
A064 Jump (hysteresis) frequency
width setting 1 0.00 to 10.00 (Hz) 0.50 ¯ {
A065 Jump (center) frequency setting
2 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
A066 Jump (hysteresis) frequency
width setting 2 0.00 to 10.00 (Hz) 0.50 ¯ {
A067 Jump (center) frequency setting
3 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
A068 Jump (hysteresis) frequency
width setting 3 0.00 to 10.00 (Hz) 0.50 ¯ {
A069 Acceleration stop frequency
setting 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
Frequency upper/lower limit and jump frequency
A070 Acceleration stop time frequency
setting 0.0 to 60.0 (s) 0.0 ¯ {
4-25
A071 PID Function Enable 00 (disabling), 01 (enabling), 02 (enabling inverted-data output) 00 ¯ {
A072 PID proportional gain 0.2 to 5.0 1.0 { {
A073 PID integral time constant 0.0 to 999.9, 1000. to 3600. (s) 1.0 { {
A074 PID derivative gain 0.00 to 99.99, 100.0 (s) 0.00 { {
A075 PV scale conversion 0.01 to 99.99 1.00 ¯ {
A076 PV source setting 00 (input via OI), 01 (input via O), 02 (external communication), 03 (pulse-string
frequency input), 10 (operation result output) 00 ¯ {
A077 Output of inverted PID deviation 00(OFF), 01 (ON) 00 ¯ {
A078 PID variation range 0. 0 to 100.0 (%) 0.00 ¯ {
PID control
A079 PID feed forward selection 00 (disabled), 01 (O input), 02 (OI input), 03 (O2 input) 00 ¯ {
4-26