Chapter 8 List of Data Settings
8 - 11
Default
Code Function name Monitored data or setting
_FF _FEF _FUF
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
Page
C038 Low-current indication signal
output mode selection 00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation) 01 ¯ {
C039 Low-current indication signal
detection level 0.0 to 2.00 x "rated current" (A) Rated current of inverter { {
4-69
C040 Overload signal output mode 00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation) 01 ¯ {
C041 Overload level setting 0.0 to 2.00 x "rated current" (A) Rated current of inverter { {
4-40
C042 Frequency arrival setting for accel. 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
C043 Frequency arrival setting for decel. 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ { 4-62
C044 PID deviation level setting 0.0 to 100.0 (%) 3.0 ¯ { 4-29
C045 Frequency arrival setting for
acceleration (2) 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
C046 Frequency arrival setting for
deceleration (2) 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 ¯ {
4-62
C052 Maximum PID feedback data 0.0 to 100.0 (%) 100.0 ¯ {
C053 Minimum PID feedback data 0.0 to 100.0 (%) 0.0 ¯ { 4-29
C055 Over-torque (forward-driving) level
setting 0. to 200. (%) 100. ¯ {
C056 Over-torque (reverse
regenerating) level setting 0. to 200. (%) 100. ¯ {
C057 Over-torque (reverse driving) level
setting 0. to 200. (%) 100. ¯ {
C058 Over-torque (forward
regenerating) level setting 0. to 200. (%) 100. ¯ {
4-65
C061 Electronic thermal warning level
setting 0. to 100. (%) 80. ¯ { 4-38
C062 Alarm code output 00 (disabling), 01 (3 bits), 02 (4 bits) 00 ¯ { 4-65
C063 Zero speed detection level 0.00 to 99.99, 100.0 (Hz) 0.00 ¯ { 4-64
Levels and output terminal status
C064 Heat sink overheat warning level 0. to 200.0 (°C) 120. ¯ { 4-68
C071 Communication speed selection 02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06
(19,200 bps) 04 ¯ {
C072 Node allocation 1. to 32. 1. ¯ {
C073 Communication data length
selection 7 (7 bits), 8 (8 bits) 7 ¯ {
C074 Communication parity selection 00 (no parity), 01 (even parity), 02 (odd parity) 00 ¯ {
C075 Communication stop bit selection 1 (1 bit), 2 (2 bits) 1 ¯ {
C076 Selection of the operation after
communication error
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02
(ignoring errors), 03 (stopping the motor after free-running), 04
(decelerating and stopping the motor) 02 ¯ {
C077 Communication timeout limit
before tripping 0.00 to 99.99 (s) 0.00 ¯ {
C078 Communication wait time 0. to 1000. (ms) 0. ¯ {
Communication function
C079 Communication mode selection 00( ASCI I), 01(Modbus-RTU) 00 ¯ {
4-113
C081 [O] input span calibration 0. to 9999., 1000 to 6553(10000 to 65530) Factory setting { {
C082 [OI] input span calibration 0. to 9999., 1000 to 6553(10000 to 65530) Factory setting { {
C083 [O2] input span calibration 0. to 9999., 1000 to 6553(10000 to 65530) Factory setting { {
C085 Thermistor input tuning 0.0 to 999.9, 1000. Factory setting { { 4-72
Adjustment
C091 Debug mode enable (Do not change this parameter, which is intended for factory adjustment.) 00 ¯ ¯
C101 Up/Down memory mode selection 00 (not storing the frequency data), 01 (storing the frequency data) 00 ¯ { 4-56
C102 Reset mode selection 00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2
(enabling resetting only upon tripping [resetting when RS is on]) 00 { {
Others
C103 Restart mode after reset 00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting
with active matching frequency) 00 ¯ {
4-54
C105 FM gain adjustment 50. to 200. (%) 100. { { 4-73
C106 AM gain adjustment 50. to 200. (%) 100. { {
C107 AMI gain adjustment 50. to 200. (%) 100. { {
C109 AM bias adjustment 0. to 100. (%) 0. { {
Meter
adjustment
C110 AMI bias adjustment 0. to 100. (%) 20. { {
4-74