Chapter 8 List of Data Settings
8 - 12
Default
Code Function name Monitored data or setting
_FF _FEF _FUF
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
Page
Ter
mi
nal
C111 Overload setting (2) 0.0 to 2.00 x "rated current" (A) Rated current of inverter { { 4-40
C121 [O] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting { {
C122 [OI] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting { {
Adjust
ment
C123 [O2] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting { {
-
C130 Output 11 on-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C131 Output 11 off-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C132 Output 12 on-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C133 Output 12 off-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C134 Output 13 on-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C135 Output 13 off-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C136 Output 14 on-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C137 Output 14 off-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C138 Output 15 on-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C139 Output 15 off-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C140 Output RY on-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C141 Output RY off-delay time 0.0 to 100.0 (s) 0.0 ¯ {
C142 Logical output signal 1 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C143 Logical output signal 1 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
4-72
C144 Logical output signal 1 operator
selection 00 (AND), 01 (OR), 02 (XOR) 00 ¯ {
C145 Logical output signal 2 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C146 Logical output signal 2 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C147 Logical output signal 2 operator
selection 00 (AND), 01 (OR), 02 (XOR) 00 ¯ {
C148 Logical output signal 3 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C149 Logical output signal 3 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C150 Logical output signal 3 operator
selection 00 (AND), 01 (OR), 02 (XOR) 00 ¯ {
C151 Logical output signal 4 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C152 Logical output signal 4 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C153 Logical output signal 4 operator
selection 00 (AND), 01 (OR), 02 (XOR) 00 ¯ {
C154 Logical output signal 5 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C155 Logical output signal 5 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C156 Logical output signal 5 operator
selection 00 (AND), 01 (OR), 02 (XOR) 00 ¯ {
C157 Logical output signal 6 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
C158 Logical output signal 6 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00 ¯ {
Output terminal operation function
C159 Logical output signal 6 operator
selection 00 (AND), 01 (OR), 02 (XOR) 00 ¯ {
4-66
C160 Input terminal response time
setting 1 0. to 200. ( ¯2ms) 1
¯ {
C161 Input terminal response time
setting 2 0. to 200. ( ¯2ms) 1
¯ {
C162 Input terminal response time
setting 3 0. to 200. ( ¯2ms) 1
¯ {
C163 Input terminal response time
setting 4 0. to 200. ( ¯2ms) 1
¯ {
C164 Input terminal response time
setting 5 0. to 200. ( ¯2ms) 1
¯ {
C165 Input terminal response time
setting 6 0. to 200. ( ¯2ms) 1
¯ {
C166 Input terminal response time
setting 7 0. to 200. ( ¯2ms) 1
¯ {
C167 Input terminal response time
setting 8 0. to 200. ( ¯2ms) 1
¯ {
Input terminal response
C168 Input terminal response time
setting FW 0. to 200. ( ¯2ms) 1
¯ {
4-72
Other
C169 Multistage speed/position
determination time 0. to 200. ( ¯10ms) 0
¯ { 4-48
4-108