STRYKER VAV USER GUIDE
362-2030—01
1.4 Icons available in the Stryker VAV Configuration ToolTable 2. Available Icons.
Tip
• Numeric values are stored in the application in a defined
unit. When these values are loaded in the configuration
wizard they may be displayed in a different unit. Each unit
has a defined precision. Because of this difference in the
precision and the unit, there may be loss of data when
loading the numeric values into the wizard and when
saving the numeric values. This loss of data is of very small
magnitude and will not affect the functioning of the
controller.
You may experience this loss during the following
scenarios.
— Setting the unit system to English and entering values
in fields such as flow set points and temperature set
points.
— Entering numeric values that are very close to the
valid range for a given field.
• When the configuration is uploaded from the device, if the
input and output configuration in the device is different from
the input and output configuration in the database then the
user configured input and output names will be lost. The
default input and output names will be displayed.
• The progress bar indicates the current progress in the
wizard. Sometimes it may take few minutes to load the
progress bar, and the progress bar will not give the
accurate progress during loading.
• Each unit has a pre-defined configuration. If the user
configures the device different from the pre-defined
configuration, the wizard displays a warning message. The
warning message is just to notify the user about the
configuration. The user can ignore the warning message
and continue with the configuration.
For Example:
—Predefined configuration: A Series Fan configuration should be combined with the Pressure Independent air flow con-
trol.
—Actual Configuration: If the user combines the Series Fan configuration with the Pressure Dependent air flow control,
the wizard displays the following warning message.
• To view all the warning messages displayed during the configuration, click the button. The warning
messages are displayed as shown in the following image.
RELATED TOPICS
“2. Configuration” on page 4
Device Icon Icon Status Description
Download State This icon indicates that th e configuration from the station has been
written to the device via the Asc Download action or the configuration
from the device has been updated in the station via the Asc Upload
action.
Download Pending State This is a download pending icon. It appears when the device is
dropped onto the Nav pane.