C6097A,B PRESSURE SWITCHES

SPECIFICATIONS

Models:

C6097A Pressure Switch: Breaks a circuit when pressure falls to scale setting. See Table 1.

Dimensions: See Fig. 1 and 2.

C6097B Pressure Switch: Breaks a circuit when pressure rises to scale setting. See Table 1.

Table 2 shows switch ratings and Table 3 shows alternate electrical ratings when used with Honeywell Flame Safeguard Programmers.

Minimum Ambient Temperature: -40°F(-40°C).

Maximum Ambient Temperature: 140°F (60°C).

1-3/32 (28)

2-21/32 (68)

27/32

(22) 1-17/32

HOLE

(90)

3-3/16

(81)

2-1/4

(57)

2-21/32 (68) 15/32 (12)

Connections (Depending on Model):

1/4-18 NPT tapping for main or high-pressure connection. 1/8-27 NPT tapping for vent or low-pressure connection (air

only).

Flange mount for connection to Honeywell Integrated Valve Train (internal vent only, no external connections).

Scale Range:

0.4to 5 in. wc (0.10 kPa to 1.25 kPa). 3 to 21 in. wc (0.75 to 5.23 kPa).

12 to 60 in. wc (3.0 kPa to 15 kPa).

1.5to 7 psi (10.3 kPa to 48 kPa).

Approvals:

13/32

31/32

(11)

(25)

 

 

2-23/32 (69)

 

1-3/4 (45)

2-13/32

(61)

25/32

(21)

2-23/32 (69)

HOUSING INDICATOR

Underwriters Laboratories Inc. listed.

Canadian Standards Association listed.

Factory Mutual: Approved.

Industrial Risk Insurers: Acceptable.

CSD-1 AFB: Acceptable.

Accessories:

32003041-001 C6097 Cover for manual reset models.

32003040-001 C6097 Cover for recycle models.

32003039-001 Position Indication Lamp Kit.

DIFFERENTIAL

GAS CONNECTION

TERMINAL DIAGRAM

 

CONNECTION

1/4 NPT WITH DUST SEAL

 

 

 

 

 

 

 

 

 

 

 

1

2

 

 

 

 

3

 

 

1/8 NPT

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

M17125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1. C6097 1/4 in. NPT Mount dimensions in in. (mm).

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1.Your local Home and Building Control Sales Office (check white pages of your phone directory).

2.Home and Building Control Customer Logistics

Honeywell Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (612) 951-1000

In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

65-0237—1

2

Page 2
Image 2