7800 SERIES EC7810A, EC7820A RELAY MODULES

Table 1B. EC7820A Terminal Ratings.

 

 

 

 

Terminal No.

Abbreviation

Description

Ratings

 

 

 

 

G

Flame Sensor Ground a

Earth G

Earth Grounda

N

Line Voltage Common (Neutral)

 

 

 

 

3

AL

Alarm (Normally Open)

220/230/240 Vac, 1A, 10A inrush for 5000 cycles.

 

 

 

 

4

FAN

Burner/Blower Motor

220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.

 

 

 

 

5

L1

Line Voltage Supply (L1)

220-240 Vac (+10%/-15%), 50/60 Hz (±10%).b

6

RT

Limits and Burner Control

220/230/240 Vac, 5A (maximum).

 

 

 

 

7

LD2

Airflow Switch Input

220/230/240 Vac, 1 mA.

 

 

 

 

8

PV1

Pilot Valve 1 (interrupted)

220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.c

9

MV

Main Fuel Valve

220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.c

10

IGN

Ignition

220/230/240 Vac, 4A at P.F. = 0.2.c

F(11)

Flame Signal

135 to 220 Vac, current limited.

 

 

 

 

13

COM

Firing Rate Common

220/230/240 Vac, 4A at P.F. = 0.5.d

14

MOD

Firing Rate Modulate

220/230/240 Vac, 4A at P.F. = 0.5.d

16

Control Voltage

220-240 Vac (+10%/-15%).

 

 

 

 

17

ES2

Preignition Interlock Input

220/230/240 Vac, 1 mA.

 

 

 

 

18

ES1

Low Fire Switch Input

220/230/240 Vac, 1 mA.

 

 

 

 

20

LOS

Lockout Input

220/230/240 Vac, 1 mA.

 

 

 

 

21

PV2

Pilot Valve 2 (Intermittent)

220/230/240 Vac, 4A at P.F.= 0.5, 20A inrush. c

22

SHTR

Shutter

220-240 Vac, 0.25A.e

aSee Table 2.

b2000 VA maximum connected load to 7800 SERIES Relay Module Assembly.

cTotal load current, excluding burner/boiler motor and firing rate outputs cannot exceed 5A, 25A inrush. d Can also be 24 Vac, 3A at PF = 0.5.

e 220-240 Vac to 120 Vac, 10 VA (minimum) stepdown transformer (not provided) required to drive shutter.

Table 2. Recommended grounding practices.

 

 

Ground type

Recommended Practice

 

 

Earth ground (subbase and relay module).

1. Use to provide a connection between the subbase and the control panel of

 

the equipment. Earth ground must be capable of conducting enough current

 

to blow the 20A fuse (or breaker) in the event of an internal short circuit.

 

2. Use wide straps or brackets to provide minimum length, maximum surface

 

area ground conductors. If a leadwire must be used, use 14 AWG copper

 

wire.

 

3. Make sure that mechanically-tightened joints along the ground path are free

 

of nonconductive coatings and protected against corrosion on mating

 

surfaces.

 

 

Signal ground (KDM, Data ControlBus

Use the shield of the signal wire to ground the device to the signal ground

Module™, Communications Interface

terminal 3(c) of each device. Connect the shield at both ends of the daisy chain

ControlBus™ Module).

to earth ground.

 

 

3

66-2040

Page 3
Image 3
Honeywell EC7820A manual Fan, Firing Rate Common 220/230/240 Vac, 4A at P.F. = 0.5.d, Wire, Surfaces