7800 SERIES EC7810A, EC7820A RELAY MODULES

Communications:

Q7700B1004 Network Interface Unit with universal 100 to 250 Vac, 50/60 Hz external power supply, external modem required.

QS7800A1001 ControlBus Module, standard. QS7800B1000 ControlBus Module, multidrop. QS7800C1009 ControlBus Module, data acquisition

modules.

QS7800D1008 ControlBus Module, Armstrong. QS7800E1007 ControlBus Module, Pulsafeeder. QS7850A1006 ControlBus Module, General Purpose

Interface.

ZM7850A1001 Combustion System Managerª Software. ZM7850B1000 SYSNetª Facilities Integration Software. S7810A1009 Data ControlBusª Module (if no KDM is

used).

S7810B1007 Data ControlBusª Module, Multi-Drop Switch Module.

Miscellaneous:

S7820A1007 Remote Reset Module.

203541 Data ControlBus Connector, 5-wire.

203765 Remote Display Mounting Bracket.

221729 Relay Module Dust Cover.

204718A Keyboard Display Module Cover, NEMA 4, clear.

204718B Keyboard Display Module Cover, NEMA 1, clear.

204718C Keyboard Display Module Cover, NEMA 4, clear with reset button.

205321B Flush Display Mounting Kit.

221818A Extension Cable, display, (1524 mm).

221818C Extension Cable, display, (3048 mm).

123514A Rectification Flame Simulator.

203659 Ultraviolet Flame Simulator.

203968A Remote Display Power Supply, 13 Vdc, plug-in.

Table 4. Flame Detection System

 

 

 

 

 

 

 

 

 

Plug-in Flame Signal Amplifiers

 

 

Applicable Flame Detectors

 

 

 

 

 

 

 

 

 

 

 

 

Flame Failure

 

 

 

 

 

 

 

Response

 

 

 

Type

Color

Self-Checking

Model

Time

Fuel

Type

Models

 

 

 

 

 

 

 

 

Rectification

Green

No

R7847A

1 or 2 sec

Gas

Rectifying

C7004, C7007, C7011.

 

 

 

 

maximum.

 

Flame Rod

Complete Assemblies:

 

 

 

 

 

 

Holdersa

C7008, C7009, Q179.

 

 

No

R7847A

1 or 2 sec

Oil

Rectifying

C7003, C7010, C7013,

 

 

 

 

maximum.

 

Photocell

C7014.b

 

 

Dynamic

R7847B

1 or 2 sec

Gas

Rectifying

C7004, C7007, C7011.

 

 

Ampli-Checkª

 

maximum.

 

Flame Rod

Complete Assemblies:

 

 

 

 

 

 

Holdersa

C7008, C7009, Q179.

 

 

Dynamic

R7847B

1 or 2 sec

Oil

Rectifying

C7003, C7010, C7013,

 

 

Ampli-Checkª

 

maximum.

 

Photocelld

C7014.b

Ultraviolet

Purple

No c

R7849A

1 or 2 sec

Gas, oil

Ultraviolet

C7027,C7035, C7044d.

 

 

 

 

maximum.

 

(Minipeeper)

 

 

 

 

 

 

 

 

 

 

 

Dynamic

R7849B

1 or 2 sec

Gas, oil

Ultraviolet

C7027,C7035, C7044d.

 

 

Ampli-Checkª

 

maximum.

 

(Minipeeper)

 

 

 

 

 

 

 

 

 

 

 

Dynamic

R7861A c,f

1 or 2 sec

Gas, oil

Ultraviolet

C7061.g

 

 

Self-Check

 

maximum.

 

 

 

 

Blue

Dynamic

R7886A c,f

2 sec

Gas, oil,

Ultraviolet

C7076.g

 

 

Self-Check

 

maximum.

coal

(Adjustable

 

 

 

 

 

 

 

Sensitivity)

 

 

 

 

 

 

 

 

 

aOrder flame rod separately; see holder instructions. b Use only Honeywell Photocell part number 38316.

c Dynamic Self-Check ultraviolet amplifiers should be used only on burners that cycle on-off at least once every 24 hours. Appliances with burners that remain on continuously for 24 hours or longer should use C7061A Flame Detector with R7861A

Amplifier.

d C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once every 24 hours. Appliances with burners that remain on continuously for 24 hours or longer should use C7061A Flame Detector with R7861A

Amplifier as ultraviolet flame detection system.

e Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the boiler if the

amplifier fails.

f Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during

burner operation and shuts down the burner if the detection system fails.

g A 220/240 Vac to 120 Vac 10 VA step-down transformer (not provided) must be used to drive the shutter.

5

66-2040

Page 5
Image 5