F120 ROOM AIR CLEANING SYSTEM

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifica- tions. This product is tested and calibrated under closely controlled conditions, and some minor differ- ences in performance can be expected if those con- ditions are changed.

Model:

F120 consists of:

—two filtered return modules with a return grille, prefilter, and

—either a 99.97% HEPA filter or a 95% DOP filter and CPZ module;

—four air supply modules with supply grilles; —a blower module with a two-speed blower, four

recirculating air supply openings, four recirculating air return openings and an optional exhaust opening;

—75 ft (23m) of six-inch diameter flexible duct; 75 ft (23m) of eight-inch diameter flexible duct;

Air Flow Capacity:

—mounting hardware kit consisting of 12 mounting brackets; 40 ft (12m) of 12-gauge high-tensile strength wire; six standard T- bar mounts; duct tape;

—seven duct collar straps.

Color:

Blower Housing: Unpainted galvanized steel.

Return and Supply Grilles: Off-white

Electrical Ratings:

 

 

120 Vac, 60 Hz

240 Vac, 60 Hz

 

 

Fan Speeda

Fan Speeda

 

 

II (high)

I (low)

II (high)

I (low)

Current

(A)

7.0

5.5

3.5

2.8

Power

(W)

800

695

800

695

aOff is “O”.

 

 

Efficiency

 

 

Air Vol cfm

 

 

Particulates at 0.3

VOC/Odors

Gas, VOC, Odor

Air Vol cfm

Model

Voltage

micron (DOP Test)

(First Pass Average)

Control Module (2)

(cu m/hr)

(cu m/hr)a

F120A 1023

120 Vac 60 Hz

95%

85%

CPZ

900 (1530)

1050 (1780)

 

 

 

 

 

 

 

F120A 1031

120 Vac 60 Hz

99.97%

900 (1530

1000 (1700)

 

 

 

 

 

 

 

F120A 1015

120 Vac 60 Hz

b

b

b

 

 

 

 

 

 

 

aWith exhaust option installed.

bPurchase filters separately.

Filters:

HEPA: High efficiency particulate air (HEPA) filter is 99.97 per- cent efficient for 0.3 micron particulates when measured with Military Standard 282 DOP test.

DOP: Hospital-grade DOP filter is 95 percent efficient for 0.3 micron particulates when measured with Military Standard 282 DOP test.

CPZ: Sorbent modules contain 11 pounds of sorbent. Adsorbs higher molecular weight hydrocarbons and oxidizes acid gases and lower molecular weight hydrocarbons.

Ambient Temperature Rating:

Shipping and Storage: -20°F to +150°F (-29°C to +66°C).

Operating: Ambient temperatures ≥90°F (32°C). Can tolerate 104°F (40°C) for brief periods.

Sound Output Rating at 3.3 ft (1m):

High Speed: 52 dBA (below ASHRAE noise criteria (NC) curve specifications for NC45 over speech recognition fre- quency range of 500 to 2000 Hz).

Low Speed: 45 dBA (below ASHRAE noise criteria (NC) curve for NC35 over speech recognition frequency range of 500 to 2000 Hz).

Installation Weight:

Blower Module: 63 lb (28.6 kg).

Supply Module: (4 required): 8 lb (3.6 kg).

Return Module without filter (2 required): 24 lb (10.9 kg).

95% DOP Filter/CPZ Module (2 required): 21 lb (9.5 kg).

99.97% HEPA Filter (2 required): 10 lb (4.5 kg).

Shipping Weight:

F120 with 95% DOP Filter and CPZ Module: 207 lb (94 kg).

F120 with 99.97% HEPA Filter: 182 lb (83 kg).

F120A1015: 152 lb (69 kg).

F120A1007: 70 lb (32 kg).

Dimensions:

See Fig. 1.

68-3042-2

2

Page 2
Image 2
Honeywell F120A1015, F120A1007 manual Specifications, Model