Installation Guide
69-2199—01 8
advaNCEd CONfiguraTiONTable 5. Advanced Configuration.
Menu Name Menu Title (LCD
top line)
Menu Options (LCD bottom
line; defaults in bold)
Menu option description Notes:
Heat Fan HEAT FAN
CONTROL
[HVAC] PANEL Fan control by HVAC In heat mode, fan controlled by HVAC or turned
on by panel in call for heat.
HVAC [PANEL] Fan control by Panel
Stage 2 Timer STAGE 2 TIMER [5 MIN] > – < [60 MIN]
[5 MIN] >
5 minutes–60 minutes Number of minutes to delay before engaging
second stage.
Purge Timer PURGE TIME [2] 3.5 5 MIN 2.0 minutes Number of minutes panel will purge following
call for heat or cool.
2 [3.5] 5 MIN 3.5 minutes
2 3.5 [5] MIN 5.0 minutes
Purge Fan FAN IN PURGE [HVAC] PANEL Fan control by HVAC Fan controlled by HVAC or panel during purge.
HVAC [PANEL] Fan control by Panel
Purge Dampers PURGE DAMPERS [UNCHANGD] OPEN Dampers Unchanged Damper position unchanged or all dampers
open during purge.
UNCHANGD [OPEN] Dampers All Open
Auto Changeover Delay CHANGEOVER
DELAY
[15] 20 30 MIN 15 minutes auto changeover timer Number of minutes to delay auto changeover
when one zone is calling for heat and another
is calling for cooling.
15 [20] 30 MIN 20 minutes auto changeover timer
15 20 [30] MIN 30 minutes auto changeover timer
DATS Enabled DISCHARGE
SENSOR
[NO] YES Disabled Enables or disables DATS. If Disabled, the
Multistage DATS Inhibit setting is Disabled.
NO [YES] Enabled
DATS High Limit DAT HIGH LIMIT [110 F] > – < [180 F]
< [160 F] >
110 deg F–180 deg F High temperature limit.
DATS Low Limit DAT LOW LIMIT [30 F] > – < [60 F]
< [40 F] >
30 deg F–60 deg F Low temperature limit.
OT Temp Enabled OT SENSOR [NO] YES Disabled Enables or disables outdoor temperature
sensor. If Disabled, the Multistage OT Temp
Lockout setting is Disabled.
NO [YES] Enabled
OT Trip Point for
Multistage Lockout
OT LOCKOUT
TEMP
[0 F] > – < [50 F]
< [50 F] >
0 deg F–50 deg F Above this temperature 2nd stage heat is
locked out.
Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES] Enabled Allow panel to downstage multistage equip-
ment when near DATS high or low limit.
[NO] YES Disabled
LCD Contrast Adjust LCD CONTRAST [1] > – < [10]
< [5] >
Contrast value 1–10 Sets LCD display contrast for ease of viewing.
Lowest contrast is 1, highest contrast is 10.
Save Changes SAVE CHANGES? [NO] YES Disabled Saves or rejects the configuration settings.
NO [YES] Enabled
Reload Defaults RELOAD
DEFAULTS?
[NO] YES Disabled Restores the panel's default configuration
settings.
NO [YES] Enabled
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 7
for instructions on using these buttons.
Press the Mode button un til the Wireless LED lights
up. The TrueZONE must be configure d for wireless
devices to select Wireless mode.
4
CONNECT WirElEss dEviCEsHOME
MODE
BACK NEXT
CONFIG
CHECK OUT
ADJUST SETTING
M28194
WIRELESS