HZ322 TrueZONE
9 69-2199—01
The HZ322 TrueZONE panel contains an LED display that communicates system and
zone status. The LEDs indicate the following information.
OpEraTiON
M28026
HZ322
HEAT 1
HEAT 2
COOL 1
COOL 2
FAN
PURGE
EM HEAT
ZONE 1
ZONE 2
ZONE 3
EMERGENCY
HEAT
Much of this information, as well as configuration information, is listed on the label
on the inside of the HZ322 cover. For users who prefer French or Spanish labels,
they are provided in form 69-2199FS. Cut them out and attach them to the inside of
the HZ322 cover.
Table 6. LED Operation.
LED Description
HEAT 1 Solid when in heat stage 1. Blinking when DATS high limit mode has
been reached.
HEAT 2 Solid when in heat stage 2. Blinking when stage 2 locked out due to
DATS or OT.
COOL 1 Solid when in cool stage 1. Blinking when DATS low limit mode has
been reached.
COOL 2 Solid when in cool stage 2. Blinking when stage 2 locked out due to
DATS.
PURGE Solid when in purge (at power-up and after a call for heat or cool).
Blinking when the DATS sensor has failed, or the wires are shorted or
open. Will blink for 3 minutes at power-up if DATS is not present.
FAN Solid with a call for fan.
EM HEAT Solid when in emergency heat mode. This light does not indicate a call
for heat. Emergency heat will only run when both HEAT and EM HEAT
are lit.
ZONE 1, 2, 3 Solid green when open or opening. Solid red when closed or closing.
Blinking amber when there is a damper or thermostat short circuit (cir-
cuit breaker trip).
Fig. 16
To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the
Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on
page 7 for instructions on using these buttons.
Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation.
Steps 11–14 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or
cool and viewing the active wires as displayed on the LCD screen.
Table 7. Checkout.
Checkout Step Line 1 display Line 2 Display Notes:
1. Display shows OT OT SENSOR VAL current OT temp (dynamic) All zone dampers open, all other relays OFF.
2. Display shows DATS DAT SENSOR VAL current DATS (dynamic)
3. Heat stages test TEST HEAT [OFF] 1 2 Heat turns on (fan also turns on if configured for
fan on in heat).
4. EM Heat stages test TEST EMERG HEAT [OFF] 1 2 Emergency heat turns on (fan also turns on).
5. Cool stages test TEST COOL [OFF] 1 2 Cooling turns on (fan also turns on).
6. Fan Test TEST FAN [OFF] ON Fan cycles on and off.
7. Damper 1 test TEST Z1 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
8. Damper 2 test TEST Z2 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
9. Damper 3 test TEST Z3 DAMPER [OPEN] CLOSED Cycles damper position with fan on.
10. View Tstat1 inputs ZONE1 STAT INPTS Displays active Tstat1 terminals or displays wire-
less thermostat operation
Tests thermostat wiring with HVAC off.
11. View Tstat2 inputs ZONE2 STAT INPTS Displays active Tstat2 terminals or displays wire-
less thermostat operation
Tests thermostat wiring with HVAC off.
12. View Tstat3 inputs ZONE3 STAT INPTS Displays active Tstat3 terminals or displays wire-
less thermostat operation
Tests thermostat wiring with HVAC off.
13. Exit checkout mode? EXIT CHECKOUT? (NEXT = EXIT)
14. Exiting checkout mode EXITING CHECKOUT
CHECkOuT