VisionPRO® IAQ
7 69-1816EFS—03
Installer system testDuring installer setup, press t
repeatedly until “Test” appears
Press s t to
select test
Test
number
Press DONE to terminate testing
System
status
Press s t to
change status
DONE
TUE
Inside
70
20
0120
DONE
1
0
TEST
System test System status Other messages
1 Cooling
system
0 Off
1 Test cooling stage 1
2 Test cooling stages 1 & 2
2 Fan system 0 Fan off
1 Fan on
3 Heating
system
0 Off
1 Test heating stage 1
2 Test heating stages 1, 2
3 Test heating stages 1, 2, 3
4 Test heating stages 1, 2, 3, 4
4 Emergency
heating
system
0 Off
1 Test EmHeat stage 1
2 Test EmHeat stages 1, 2
5 Humidifier 0 Off
1 On
6 Dehumidifier 0 Off
1 On
7 Ventilator 0 Off
1 On
P Ventilation meets ASHRAE 62.2
standard (Function 0404)
F Ventilation does not meet ASHRAE
62.2 standard (Function 0404)
Err See error codes
CAUTION: EQUIPMENT
DAMAGE HAZARD. Compressor
protection is bypassed during
testing. To prevent equipment
damage, avoid cycling the com-
pressor quickly.
1. Enter the Installer System Test by entering
Installer Setup.
2. The test appears at the end of the Installer
Setup Numbers.
3. See above for available Installer System
Tests.
4. If installed with a Discharge Air
Temperature Sensor (ISU365=1), press
MORE to view the discharge temperature,
and press CANCEL to return to the Installer
test screen.
How to Use the Installer System Test
The Installer Test is part of the Installer Setup Menu.