MS-5UD & MS-10UD Series Fire Alarm Control Panel

Operating Instructions

NORMAL - Only AC POWER is illuminated green.

All other indicators are off. LCD display will read SYSTEM ALL NORMAL.

PANEL KEY - The key to open the panel can be found at the following location:

WHEN AUDIBLE DEVICES ARE SOUNDING -

FOR AN ALARM

1.Evacuate the protected area

2.Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what your current status is.

Phones: ____________________________

_________________________________

Fire Department

Monitoring Service

3. If the Fire Department is responding, be prepared to provide directions to arriving firefighters.

FOR TROUBLE ONLY

1.Notify the monitoring service and/or Fire department if this panel is connected to either one, and tell them what is happening.

2.Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE/STEP button. The TROUBLE indicator will remain illuminated yellow. Contact authorized service personnel immediately! (See Below).

WARNING!

DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM.

THE PROTECTION THE SYSTEM OFFERS HAS BEEN COMPROMISED, OR ELIMINATED WHEN A

TROUBLE CONDITION EXISTS.

To return to normal after an alarm

1.Do not enter the protected area until safe to do so.

2.Clear all initiating devices. Smoke detectors will not reset if there is still smoke in the area.

3.Reset the control panel (PRESS the RESET button)

Power failure or brownout

If AC power drops too low or fails, AC POWER indicator will extinguish, the system TROUBLE indicator will turn on yellow, and the panel buzzer and any other audible trouble devices will sound. Contact authorized service personnel immediately. See below.

In the event of trouble, contact the local Fire-Lite Service Representative

Name:_____________________________________

Company: _________________________________

Address:___________________________________

Telephone Number: ________________________

Manual activation (Fire Drill or otherwise)

Notification Appliance Circuits (NACs) can be activated by pressing and holding the DRILL button for at least two seconds.

NOTE: You may want to disconnect municipal box by sliding DISCONNECT switch, located on 4XTMF module, to its disconnect position (to the right). If a DACT is con- nected, notify the monitoring service before conducting any fire drills or tests.

Alarm Silencing

Notification Appliance Circuits may be silenced by pressing the ALARM SILENCE button. ALARM SILENCED will turn on yellow. Subsequent alarms will reactivate circuits. Press the RESET button to clear the "silenced" condition.

NOTE: Notification Appliance Circuits may be programmed as nonsilenceable. Also, Signal Silence Inhibit, if enabled, will prevent silencing of NACs for one minute after an alarm (see manual).

To test the indicators, LCD display and piezo

Press and release the RESET button and check all indicators/ LEDs. Every indicator/LED should be on, LCD shows all pixels on, piezo sounder beeps.

For more information, refer to the MS-5UD & MS-10UD Series Manual, Document #52626. It is kept in the following location:

THIS SHEET SHALL BE FRAMED ADJACENT TO

THE CONTROL PANEL

Document #52805 Rev. A 10/05/06 ECN 05-765

Page 1
Image 1
Honeywell MS-10UD, MS-5UD manual For AN Alarm, For Trouble only, This Sheet Shall be Framed Adjacent to Control Panel

MS-5UD, MS-10UD specifications

The Honeywell MS-10UD and MS-5UD are advanced fire alarm control panels designed for optimal performance and reliability in commercial and industrial applications. Both models are part of Honeywell’s esteemed line of fire safety solutions, catering to different operational scales and requirements.

The MS-10UD is a sophisticated system that supports up to ten addressable devices on a single loop. It is ideal for larger facilities that require extensive monitoring capabilities. This panel is equipped with a multitude of features including a built-in digital communicator for remote notifications, a large LCD display that provides clear status information, and a programmable user interface for enhanced operational control. Its flexibility allows for easy expansion or integration with existing security systems, which is critical for evolving safety needs.

On the other hand, the MS-5UD is designed for smaller applications, supporting up to five addressable devices. Despite its compact size, this panel does not skimp on features. It includes an intuitive user-friendly interface that simplifies system management, along with robust communication options such as event logging and reporting. Both panels are built with resilience in mind, boasting components that resist dust and temperature fluctuations, ensuring prolonged durability in various environments.

Both models utilize Honeywell's patented technologies, such as the QuickConnect feature, allowing for swift installation and simplified device management. This leads to reduced installation costs and minimal downtime during commissioning. Moreover, their compatibility with a wide range of Honeywell addressable detectors and modules ensures comprehensive coverage for fire detection.

In terms of alarm signaling, both the MS-10UD and MS-5UD are designed to accurately detect and alert users in the event of a fire hazard. They support a variety of notification appliances, ensuring clear and timely alerts to occupants and emergency services. Additionally, both systems comply with rigorous industry standards and certifications, making them reliable choices for a wide variety of applications.

In summary, the Honeywell MS-10UD and MS-5UD fire alarm control panels represent a blend of advanced technology, user-friendly design, and robust performance. Their deployment can significantly enhance safety protocols within any facility, providing peace of mind through proactive monitoring and rapid response capabilities.