Addressable Fire Alarm Control Panel
MS-9600LS/MS-9600LSE
MS-9600UDLS/MS-9600UDLSE
MS-9600LSC
Manual
Contents
Main
2MS-9600LS Series Manual P/N 52646:B2 2/12/2010
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
FCC Warning
Software Downloads
Documentation Feedback
Table of Contents
Page
Page
Page
Before proceeding, the installer should be familiar with the following documents.
10 MS-9600LS Series Manual P/N 52646:B2 2/12/2010
Notification Applicance Circuits
AHJ (Authority Having
Notification Appliance Circuits
1 Fixed Trouble Relay
Peripheral Devices and Their Documents:
Page
Section 1: Product Description
1.1 Inventory
1.2 Features and Options
Page
1.3 Specifications
Page
1.3.1 Current Availability
1.4 Controls and Indicators
HONEYWELL LIFE SAFETY SYSTEM ALL NORMAL 10:00A 020102
1.5 Circuits
1.6 Components
1.6.1 Intelligent Addressable Detectors: Newer Series
1.6.2 Intelligent Addressable Modules: Newer Series
1.6.3 300 Series Intelligent Addressable Devices
1.6.4 Addressable Device Accessories
1.7 Optional Modules
1.8 Accessories
1.8.1 PS-Tools Programming Utility
1.8.2 Dress Panel: DP-9692
1.8.3 TR-CE Trim Ring
1.8.4 Battery Box
1.8.5 Battery Charger
CHG-75 Battery Charger
1.8.6 New ANN-BUS Annunciators/Devices
ANN-BUS Wiring
!
Page
Page
ANN-BUS Device Addressing
ANN-80 Remote Fire Annunciator
Page
Page
ANN-S/PG Serial/Parallel Interface Installation
Page
ANN-I/O LED Driver Module*
+ - + - + - + -
ANN-LED Annunciator Module*
Page
ANN-RLY Annunciator Module
Page
ANN-BUS Audio Panel Control
Page
1.8.7 Legacy ACS Annunciators
1.9 Getting Started
Page
Section 2: Installation
2.1 Mounting
MS-9600LS Series Manual P/N 52646:B2 2/12/2010 43
Mounting Installation
Figure 2.1 FACP Main Circuit Board Installation
44 MS-9600LS Series Manual P/N 52646:B2 2/12/2010
Figure 2.2 FACP Cabinet Mounting
Installation Mounting
Hinge Slot for optional Dress Panel
MS-9600LS Series Manual P/N 52646:B2 2/12/2010 45
Mounting Installation
Figure 2.3 FACP Cabinet Dimensions
2.2 Power
2.2.1 AC Power and Earth Ground Connection
2.2.2 Battery Power
2.2.3 Special Application DC Power Output Connection
2.3 Relays
2.4 Notification Appliance Circuits
2.4.1 Configuring NACs
MS-9600LS Series Manual P/N 52646:B2 2/12/2010 49
Notification Appliance Circuits Installation
2.4.2 Style Y (Class B) NAC Wiring
2.4.3 Style Z (Class A) NAC Wiring
Figure 2.8 NAC Style Z (Class A) Wiring
Figure 2.7 NAC Style Y (Class B) Wiring
2.5 Power-limited Wiring Requirements
2.6 Optional Modules and Devices
2.6.1 DACT-UD2 Installation
Page
Page
2.6.2 4XTMF Transmitter Module Installation
2.6.3 Auxiliary Trouble Input (J16 & J17)
2.6.4 SLC-2LS Expander Module
2.6.5 Printer/PC
2.6.6 Annunciators
Legacy ACM-8RF Relay Control Module
!
Page
Section 3: Programming
3.1 Programming Data Entry
3.2 User Programming
SYSTEM ALL NORMAL 10:00A 010807
1=READ STATUS 2=PROGRAMMING 3=REMOTE DOWNLOAD
3.3 Initial Power-up
3.4 Programming Screens Description
3.5 Programming and Passwords
TROUBL IN SYSTEM NO DEVICES INSTALLED 09:03A 020410
Page
3.6 Master Programming Level
3.6.1 Autoprogram
3.6.2 Point Program
Page
Page
Page
Page
Page
Page
Page
Page
Page
DESCRIPTION 1D002
Page
Page
Page
Page
Page
MS-9600LS Series Manual P/N 52646:B2 2/12/2010 83
Monitor module type selection will affect the function of the point as follows:
Table 3.1 Monitor Types
3 For all entries ending in AR, AR refers to AutoResettable.
4 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to Monitor Module Operation on page 198.
MON ZONE ASSIGN
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Page
Page
DESCRIPTION 1M012
Page
Page
Page
Page
Page
Page
DESCRIPTION 1M002
3.6.3 Zone Setup
Disable
Zone 97, 98 and 99
ZONE TO DISABLE Z
SPEC PURPOSE ZONE 1=PAS 97 OFF 2=PRESIGNAL 98 OFF 3=TWO STAGE 99 OFF
Page
Page
3.6.4 Loop Setup
Loop Protocol
3.6.5 System Setup
Page
Page
Page
DAYLIGHT SAVINGS 1=ENABLED YES 2=START MONTH MAR 3=START WEEK WEEK-2
DAYLIGHT SAVINGS 1=END MONTH NOV 2=END WEEK WEEK-1
Page
WATERFLOW DELAY RANGE 0-90 SECONDS
AC LOSS DELAY 1=NO DELAY 2=ENTER DELAY
Page
Page
NAC TYPE 1=BELL 2=HORN 3=STROBE
Page
Page
Relays
NAC SYNC TYPE 1=SYSTEM SENSOR 2=WHEELOCK 3=GENTEX
RELAYS 1=RELAY 1 2=RELAY 2 3=RELAY 3
Page
Waterflow Silenceable
3.6.6 Verify Loops
VERIFY LOOPS 1=LOOP 1 2=LOOP 2 3=BOTH LOOPS
VERIFYING LOOPS PLEASE WAIT
3.6.7 History
3.6.8 Walktest
3.6.9 Option Modules
NO POINTS IN SYSTEM
UNTESTED POINTS 010 1D001 SMOKE (PHOTO) ********************* NOT TESTED
WALKTEST RESULTS
Page
Page
Page
Page
Page
Page
Page
Page
Page
ANN-RLED Module #1
ANN-RLED Module #2
ANN-LED Module #1
ANN-LED Module #2
ANN-RLED Module #2 (Point Range 31 - 60)
ANN-RLED Module #1 (Point Range 01 - 30)
ANN-LED Module #2 (Point Range 11 - 20)
ANN-LED Module #1 (Point Range 01 - 10)
ANN-RLY - ADDR. # 1=RELAY 1 ZONE 00 2=RELAY 2 ZONE 01 3=RELAY 3 ZONE 02
ANN-BUS AUTO-CONGFIGURE IN PROGRESS PLEASE WAIT
Page
ANN-80 OPTIONS 1=PIEZO ENABLE 2=LOCK ENABLE 3=ACK BTN ENABLE
ANN-80 OPTIONS 1=SIL BTN ENABLE 2=RST BTN ENABLE 3=DRL BTN ENABLE
Page
3.6.10 Password Change
3.6.11 Clear Program
3.6.12 Program Check
3.7 Maintenance Programming Level
3.7.1 Disable Point
3.7.2 History
3.7.3 Program Check
3.7.4 Walktest
3.7.5 System
3.7.6 Zone Setup
Page
Zones Installed
Zones Enabled
ZONES INSTALLED 00 01 02 03 04 05
ZONES ENABLED 00 01 02 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Page
Page
Page
Section 4: Operating Instructions
4.1 Panel Control Buttons
4.1.1 Acknowledge/Step
4.1.2 Alarm Silence
4.1.3 Drill/Hold 2 Sec
4.3 Normal Operation
HONEYWELL LIFE SAFETY SYSTEM ALL NORMAL 10:00A 010810
4.4 Trouble Operation
TROUBL SMOKE (PHOTO) <ADJ> <NOUN> INVREP 10:00A 010810 1D001
4.5 Alarm Operation
ALARM PULL STATION <ADJ> <NOUN> Z000 10:00A 010810 1M001
4.6 Supervisory Operation
4.7 Process Monitor Operation
4.8 Hazard Condition Operation
ACTIVE SUPERVISORY <ADJ> <NOUN> Z000 10:00A 010810 1M001
4.9 Medical Alert Condition Operation
4.10 Programmed Zone Operation
4.11 Disable/Enable Operation
4.12 Waterflow Circuits Operation
4.13 Detector Functions
4.14 Time Functions: Real-Time Clock
4.15 NAC Operation
4.16 Synchronized NAC Operation
4.17 Coded Operation
4.18 Presignal
4.19 Positive Alarm Sequence
4.20 Special System Timers
4.20.1 Silence Inhibit Timer
4.20.2 Autosilence Timer
4.20.3 Trouble Reminder
4.20.4 Waterflow Retard Timer
4.21 Walktest
4.22 Read Status
Page
4.22.1 System Point
4.22.2 Zones
4.22.3 Power
4.22.4 Trouble Reminder
4.22.5 Timers
4.22.6 NAC
4.22.7 Relays
4.22.8 Program Check
4.22.9 History
4.22.10 Annunciators
Page
4.22.11 Phone Line
4.22.12 Central Station
4.22.13 Service Terminal
4.22.14 Printer/PC
4.22.15 Print
PRINT 1=HISTORY 2=WALKTEST LOG 3=DETECTOR DATA PRINT 1=EXIT PRINTING
Page
4.22.16 Time-Date
Section 5: Power Supply Calculations
5.1 Overview
5.2 Calculating the AC Branch Circuit
5.3 Calculating the System Current Draw
5.3.1 Overview
5.3.2 How to Use Table 5.3 on page176 to Calculate System Current Draw
176 MS-9600LS Series Manual P/N 52646:B2 2/12/2010
Power Supply Calculations Calculating the System Current Draw
Calculation Column 1 Primary, Non-Fire Alarm Current (amps)
Calculation Column 2 Primary, Fire Alarm Current (amps)
Table 5.3 System Current Draw Calculations
5.4 Calculating the Battery Size
5.4.1 NFPA Battery Requirements
5.4.2 Selecting and Locating Batteries
Appendix A: Software Zones
A.1 Correlations
Correlation of Input and Output Zones
Table A.1 Detector Programming Sheet Example
Table A.2 Module Programming Sheet Example
Table A.3 Blank Detector Programming Sheet - 1 of 2
Table A.4 Blank Detector Programming Sheet - 2 of 2
Table A.5 Blank Module Programming Sheet - 1 of 2
Table A.6 Blank Module Programming Sheet - 2 of 2
Appendix B: Default Programming
The following table provides a list of the programming options and their factory default settings.
Appendix C: NFPA Standard-Specific Requirements
188 MS-9600LS Series Manual P/N 52646:B2 2/12/2010
NFPA Standard-Specific Requirements
Table C.1 411UDAC Connections to FACP
Figure C.1 Central Station Service Using 411UDAC
MS-9600LS Series Manual P/N 52646:B2 2/12/2010 189
NFPA Standard-Specific Requirements
Figure C.2 FACP Connection to 411UD
+ -
Table C.2 411-UD Connections to FACP
FIRE
Page
Page
C.1 Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts
C.2 MBT-1 Municipal Box Trip - Silenceable
Appendix D: FACP with Keltron
!
Appendix E: Wire Requirements
Table E.1 FACP Wire Specifications
MS-9600LS Series Manual P/N 52646:B2 2/12/2010 197
NAC Wiring Wire Requirements
E.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
Table E.2 NAC Wiring Requirements for FACP
Appendix F: HVAC Control
F.1 Control Module Operation
F.1.1 HVAC SHUTDN
F.2 Monitor Module Operation
F.2.1 HVAC RESTART
F.2.2 HVAC OVRRIDE
Appendix G: Canadian Application
Index
Numerics
A
B
C
D
E
F
G
H
I
K
O
P
R
S
T
U
V
W
Z
Manufacturer Warranties and Limitation of Liability