9
IInput values are always changed using the or key with
the key held down.
IInput parameters, e.g. the switching difference is shown as “E”
with a 2-digit number, e.g. “E 01”.
IAccess to the programming levelis by pressing the and
key at the same time for 5 seconds.
The parameters to be changed can then be accessed by pressing
the and keys.
ITo exit from the programming leveland save the data, press
the key after the last input parameter. If no key is pressed in the
programming level for 10 minutes, this mode will be exited
without the data being saved.
IDo not display altered parameter data before saving the data, as it
would be reversed to its original value in the process.
6.4 Setting the cold store temperature
Press and hold down the key. Adjust the setpoint on the value
in question using the or key.
Adjustment is possible within the limits of the input parameters E01
and E02.
The factory setting is +4°C.
6.5 Manual defrost
Press and hold down the key for 5 seconds. The manual defrosting
process will be initiated by forcibly de-energizing the relay.
If parameter E09 is set to 0: no defrosting will be started.
7 Programming
Access to the programming level:
IPress and hold down firmly the and keys at the same time
for approx. 5 seconds. (E00 appears on display.)
IUse or key to select parameters.
ISetting: Press and hold down the key. Adjust the setpoint value
to the desired figure using the or key.
IDo not display altered parameter data before saving the data, as it
would be reversed to its original value in the process.