Honeywell PCR-300 RC manual Housing with 2 mounting tabs, Housings with 1 mounting tab

Models: PCR-300 RC PCR-300

1 20
Download 20 pages 41.75 Kb
Page 6
Image 6

a)housing with 2 mounting tabs:

open out the lateral mounting tabs; clip the unit on the 35 mm rail and press tabs in again.

b)housings with 1 mounting tab:

put housing on the upper 35 mm rail. Clip the unit on the 35 mm rail, lower tab clips on the rail automatically. To remove the unit from the rail press in lower mounting tab with a screw driver, lift unit.

IMounting of sensor:

IUse a cable clamp to secure sensor T1 in a suitable position.

ISecure evaporator sensor T2 in the evaporator fin core at the point where it is suspected icing is the greatest. It is advisable to use a point in the lower third of the finned evaporator.

5.2Electrical installation

CAUTION: The mains voltage and system frequency must be the same as the nominal values on the device’s rating plate.

Work on electrical systems must be performed by qualified personnel. Relevant local safety regulations must be observed.

Wiring diagram:

6

Page 6
Image 6
Honeywell PCR-300 RC manual Housing with 2 mounting tabs, Housings with 1 mounting tab, Mounting of sensor