Honeywell user manual RDD100 User Guide, Display Units List, PSI Multiplier, Units Description

Models: RDD100

1 7
Download 7 pages 2.4 Kb
Page 5
Image 5
Display Units List

RDD100 User Guide

Resp

*99WE

(Command Echo)

Type

*99du= {selection-see DU list below}

(A list of available pressure display units can also be found in the associated transducer User’s Manual.)

Resp *99DU= {selected display units} (Command Echo)

 

Display Units List

Display Unit

PSI Multiplier

Units Description

ATM

0.068046

ambient atmosphere at sea level

BAR

0.068948

bar (105 newtons/meter2)

CMWC

70.304

centimeters of water column (4ºC)

FTWC

2.3065

feet of water column (4ºC)

INHG

2.0360

inches of mercury (0ºC)

INWC

27.679

inches of water column (4ºC)

KGCM

0.070307

kilograms/centimeters2

KPA

6.8948

kilopascal

MBAR

68.948

millibar (1 hectopascal)

MMHG

51.714

millimeters of mercury (0ºC) or torr

MPA

0.0068948

megapascal

MWC

0.70304

meters of water column (4ºC)

PSI

1.0000

pounds per square inch

USER

0.0010000-999.99

user supplied

LCOM

FS=60000

logic common value (1)

PFS

FS=100.000

percent of full scale in 0.001%

 

 

Increments

(1) The LCOM display unit (logic common) automatically switches the digital pressure output to a scale, which has 60000 as the full scale output. The output will have a decimal point in the same position as it was in the original psi scale. For example, when a 10 psia device is switched to DU=LCOM, the full scale digital pressure output will be 60.000, instead of 10.000. Also, a 500 psi device will output full scale 600.00 instead of 500.00. PFS generally provides the highest readout resolution available when using the RDD100 readout.

2.5“Continuous Transmit” Mode

Type

*99we<cr>

 

Resp

*99WE

(Command Echo)

Type

*99mo=p2<cr>

(Continuous Pressure Transmit Command)

Resp

*99MO=P2

(Command Echo)

2.6Changes Stored In EEPROM

Type

*99we<cr>

(Write Enable Command)

Resp

*99WE

(Command Echo)

Type

*99sp=all<cr>

(Store Parameters Command)

Resp

*99SP=ALL

(Command Echo)

2.7Verifying Stored Parameters

After cycling power to the transducer the RDD100 should now display pressure readings in the selected display units. If there is a need to interrogate the transducer to observe its set-up parameters, this can be done using the following sequence:

Type

*99du<cr>

Resp

*99DU=INHG (If transducer is set to read inches of mercury)

Although the Display Units example was used, this method of interrogation will work with any of the set up parameters, listed above and in the associated User’s Manuals.

Note: Since pressure units are not a part of the RDD100 display, the user may want to attach a sticker or some other indication of the pressure units either on or near the display window.