A.5 Configuring Smart Meter Using Pushbuttons, Continued

Transmitter Output Conformity and Smart Meter Configuration, continued

If you select pressure type engineering units, you cannot set the lower or upper display limits. These values are automatically set when you select the engineering units.

You can set only the upper display limit when the transmitter is configured for SQUARE ROOT output conformity. The lower display limit is fixed at zero (0) for a transmitter in square root mode and cannot be changed.

You can set both the lower and upper display limits when you have selected custom engineering units (EUF) and the

transmitter output conformity is set to LINEAR.

When setting the lower and upper display limits, if you let either the lower or upper display limit setting time out (after thirty seconds), the meter will discard the newly set values and will revert to its previous settings. The meter forces you to set both limits by automatically initiating the next limit setting, either lower or upper, depending upon which limit you set first.

3. If you change the transmitter’s output conformity, you must reconfigure the smart meter as outlined in Tables A-5, A-7 and A-8.

Table A-4 Smart Meter Engineering Units Code

Smart Meter Code

Engineering Unit

Transmitter Output

 

 

 

Conformity

EU0

%

*

Linear or Square Root

 

 

 

 

EU1

in H2O

*

 

EU2

mmHg

*

 

 

 

 

 

EU3

PSI

*

 

EU4

kPa

 

 

 

 

 

EU5

MPa

 

 

 

 

 

EU6

mbar

Linear

EU7

bar

 

EU8

g/cm2

 

EU9

kg/cm2

 

EUA

mmH2O

 

EUB

inHg

 

EUC

mH2O

 

EUD

GPM

*

Square Root

 

 

 

 

EUE

GPH

*

Square Root

EUF

Custom

Linear or Square Root

*These selections have indicators on smart meter display.

† Use stick-on labels provided for other engineering units.

60

ST 3000 Release 300 Installation Guide

2/05