A.5

 

 

Configuring Smart Meter Using Pushbuttons, Continued

Setting Lower Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Values, continued

 

 

 

 

 

 

 

 

 

 

 

 

Table A-7

Setting Lower Display Values for Smart Meter Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step

 

 

 

 

Action

 

 

 

 

Meter Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

You have completed units selection in Table

If lower limit display value was previously set,

 

A-5 and U-Lappears on the display. Press

KNOWN VALUE indicator lights and set value

 

LOWER VALUE button to initiate lower

flashes in display.

 

 

 

 

display limit setting function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VAR

 

 

 

 

 

 

UPPER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

 

This procedure is only

 

 

SEL.

 

 

 

 

 

 

VALUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

%

 

 

100

 

 

 

 

 

 

 

 

 

 

 

applicable for Custom (EUF) engineering unit

 

 

 

 

 

 

 

 

 

0 .00

 

 

S E T

 

 

 

 

 

 

 

 

 

 

 

 

UNITS

 

selection in a transmitter configured for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINEAR output conformity.

 

 

 

 

 

 

ANALOG

 

LOWER

 

 

 

 

 

 

 

 

KNOWN VALUE

 

VALUE

 

 

 

 

 

 

 

 

 

 

 

 

The lower display value for transmitters

 

 

 

 

 

 

 

 

 

 

 

 

 

Previously set

 

 

 

 

 

 

 

 

configured for SQUARE ROOT output

 

value flashes in

 

 

 

 

 

 

 

 

conformity is fixed at zero (0.00) and cannot

 

display and

 

 

 

 

 

 

 

 

 

indicator lights

 

 

 

 

 

 

 

 

be changed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Press LOWER VALUE button again within 5

Display shows magnitude range selection.

 

seconds. Otherwise, meter exits limit setting

 

 

 

 

 

 

 

 

 

 

 

 

function.

 

 

 

VAR

 

 

 

 

 

 

UPPER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEL.

 

 

 

 

 

 

VALUE

 

 

 

 

 

 

0

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

19 .99

 

 

UNITS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S E T

 

 

 

 

 

 

 

 

 

 

 

ANALOG

 

LOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

 

The magnitude range

 

 

 

 

 

 

 

 

 

 

 

selection only applies for setting the display limits. This selection does not affect the normal operation of the meter. During normal operation, the display is automatically ranged to provide the best precision possible.

Continued on next page

64

ST 3000 Release 300 Installation Guide