A.5

Configuring Smart Meter Using Pushbuttons, Continued

Setting Upper Display

 

The procedure in Table A-8 outlines the steps for setting the upper

Values

 

 

display limit to represent the 100 percent (URV) output of the

 

 

 

 

transmitter.

 

 

 

This procedure applies only for Flow units (GPM or GPH) in a

 

ATTENTION

 

 

 

 

 

transmitter configured for SQUARE ROOT output conformity, or

 

 

 

 

CUSTOM unit in a transmitter configured for linear or square root

 

 

 

 

output conformity.

Table A-8

Setting Upper Display Value for Smart Meter Display

 

 

 

 

 

 

 

 

 

Step

 

Action

 

Meter Display

 

 

 

 

 

 

1

Press UPPER VALUE button to initiate upper

If upper limit display value was previously set,

 

display limit setting function.

KNOWN VALUE indicator lights and set value

 

 

 

flashes in display.

 

 

 

 

 

2

Press UPPER VALUE button again within 5

Display shows magnitude range selection.

 

seconds. Otherwise, meter exits limit setting

 

 

 

 

 

 

function.

VAR

 

 

 

UPPER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEL.

 

 

 

VALUE

 

 

 

0

 

 

100

 

 

 

%

 

 

 

 

 

19 .99

 

UNITS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S E T

 

 

 

 

ANALOG

 

LOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALUE

ATTENTION

The magnitude range

 

selection only applies for setting the display limits. This selection does not affect the normal operation of the meter. During normal operation, the display is automatically ranged to provide the best precision possible.

Continued on next page

68

ST 3000 Release 300 Installation Guide

2/05