A.5 Configuring Smart Meter Using Pushbuttons, Continued

Selecting Engineering Units

The procedure in Table A-5 outlines the steps for selecting the desired engineering units for a smart meter using its local adjustments on the face of the meter. You will be selecting the unit of measurement that you want the smart meter to indicate during normal operation.

 

WARNING

When the transmitter’s end-cap is removed, the housing is not

 

 

explosionproof.

 

Table A-5

Selecting Engineering Units

 

 

 

 

 

 

Step

Action

Meter Display

1Loosen lock on meter end-cap and unscrew cap from housing. Be sure transmitter power is ON.

2

Press UNITS SET button.

Display shows code for current engineering

 

 

units setting.

 

 

 

 

 

VAR

 

 

UPPER

 

 

SEL.

 

 

VALUE

 

 

0

%

100

 

 

 

EU0

 

UNITS

 

 

 

 

%

S E T

 

 

 

 

 

 

 

 

ANALOG

 

LOWER

 

 

 

 

 

 

 

 

 

 

VALUE

3

Press Increase ￿ key to call up next code or

Selection codes for engineering units

 

Decrease ￿ key to call up previous code.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repeat this action until desired code is on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

display.

 

VAR

 

 

 

 

 

 

 

 

 

 

 

UPPER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can hold down the Increase or Decrease

 

 

 

 

 

 

 

 

 

 

 

 

SEL.

 

 

 

 

 

 

 

 

 

 

 

VALUE

 

key to scroll forward or backward through the

 

 

%

 

 

 

 

 

 

 

 

 

0

 

100

UNITS

 

codes.

 

EU1

 

 

 

 

 

S E T

 

 

 

 

 

 

 

 

 

 

ANALOG

In H2O

LOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

Remember that if transmitter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is configured for SQUARE ROOT output

Press and hold to

 

 

 

 

 

 

 

 

 

 

Press and hold to

 

scroll backward

 

 

 

 

 

 

 

 

 

 

 

conformity the only valid code selections are

 

 

 

 

 

 

 

 

 

 

scroll forward

 

through selections

 

 

 

 

EU0 = %*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

through selections

 

 

 

EU0 (%)

 

 

 

 

 

 

EU1 = inH2O*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EU2 = mmHg*

 

 

 

 

 

 

 

 

 

 

EUD (GPM)

 

 

 

 

 

 

EU3 = PSI*

 

 

 

 

 

 

 

 

 

 

 

EUE (GPH)

 

 

 

 

 

 

EU5 = MPa

 

 

 

 

 

 

 

 

 

 

 

EUF (Custom)

 

 

 

 

 

 

EU4 = KPa

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EU6 = mbar

 

 

 

 

 

 

 

 

 

If transmitter is configured for LINEAR output

 

 

 

 

 

 

EU7 = bar

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EU9 = Kg/cm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EU8 = g/cm2

 

 

 

 

 

 

 

 

 

conformity EU0 (%) to EUC and EUF

 

 

 

 

 

 

EUA = mmH2O

 

 

 

 

 

 

 

 

(CUSTOM) are valid code selections.

 

 

 

 

 

 

EUB = inHg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EUC = mH2O

 

 

 

 

 

 

*These selections

 

 

 

 

 

 

 

 

 

 

EUD = GPM*

 

 

 

 

 

 

have indicators on

 

 

 

 

 

 

 

 

 

 

EUE = GPH*

 

 

 

 

 

 

the display.

 

 

 

 

 

 

 

 

 

 

EUF = Custom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page

2/05

ST 3000 Release 300 Installation Guide

61