60-1147-43
Fig. 4—Wiring connections.
2. Carefully remove and discard the polystyrene packinginsert that protects the mercury switches during shipment.3. If LED indication (EM.HT., CHECK, etc.) is to be usedwith the Q674 Subbase, install the preprinted insert under thethermostat set point scale (Fig. 8). To install, push boththermostat set point levers to the far ends of the thermostat. Useindex finger to gently pull out the plastic set point scale about1/4 in. [6 mm]. Drop insert into recessed area behind set pointscale so that selected LEDs show. Make sure insert is com-pletely seated in recessed area. Let set point scale pop back, andset levers to desired positions.FOR STRAIGHT
INSERTION–
STRIP 5/16 in. [8 mm]
FOR WRAPAROUND–
STRIP 7/16 in. [11 mm]
SUBBASE TERMINAL SCREW
M928
BARRIER
Fig. 5—Internal schematic and typical wiring diagram for T874N and Q674C.
M1860
G
R
W2
X
L1
(HOT)
L2
AUTO
SYSTEM
SWITCH
AUTO
ON
FAN
SWITCH
1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS
REQUIRED.
1
CHECK
LED
(GRN)
L
Y
OFF
H1
ANTICIPATOR
RISE
W3
W1
FAN RELAY
DEFROST RELAY
CONTACT
C1
C1
ANTICIPATOR
FALL
H2
HEAT
RELAY 1
COMPRESSOR
CONTACTOR
EM. HT. RELAY
CONTACT
EM. HT. RELAY
CONTACT
OUTDOOR
THERMOSTAT
HEAT
RELAY 2
HEAT
RELAY 3
REVERSING
RELAY
OPTIONAL
COMPRESSOR
FAILURE
DEVICE
CO
H2 ANTICIPATOR
FALL
H1