4. Configuration
4.1Configuration Menus (See following pages for explanations) NOTE: Factory settings are inside the shaded cells.
TB7980A model
|
|
|
|
|
|
|
|
|
|
| Application |
| Default mode & |
| NSB value |
| Output 1 | Maximum | Minimum |
|
| Output 1 type |
|
| min. opening | setpoint | setpoint | ||
| (section 4.2) |
|
| (section 5.6) |
| ||||
|
| (section 4.3.1) |
|
| (section 4.3.2) | (section 4.6) | (section 4.6) | ||
|
|
|
|
|
| ||||
0 | Internal sensor | 0 | Cool / | 1 | 2°F (1°C) | 0 | 0% |
|
|
1 | Room | 1 | Heat / | 2 | 4°F (2°C) | 1 | 10% | Can be set | Can be set |
2 | Return | 2 | Cool / | 3 | 6°F (3°C) | 2 | 20% | between 95°F | between 50°F |
3 | Supply | 3 | Heat / | 4 | 8°F (4°C) | 3 | 30% | (35°C) and | (10°C) and |
|
|
|
|
|
|
|
| ’’minimum | ’’maximum |
4 | Auto changeover |
|
| 5 | 10°F (5°C) | 4 | 40% | ||
|
| setpoint + 1’’ | setpoint - 1’’ | ||||||
5 | Limited cooling |
|
| 6 | 12°F (6°C) | 5 | 50% | ||
|
|
|
| ||||||
|
|
|
| 7 | 14°F (7°C) |
|
| Default value | Default value |
|
|
|
|
|
|
|
| is 95°F (35°C) | is 50°F (10°C) |
|
|
|
| 8 | 16°F (8°C) |
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
| 9 | 18°F (9°C) |
|
|
|
|
1.Remove the thermostat from its base and set the SW2 switch to MENU.
2.Reinstall the thermostat. The thermostat is now in configuration mode. The first digit flashes to indicate that the first item of the menu can now be modified.
3.To modify the setting, use the up/down arrows. Refer to the adjacent tables.
4.Press Override to save the new setting and go to the next item.
5.Repeat steps 3 and 4 for remaining items.
6.When the configuration is done, set the SW2 switch back to NORMAL.
TB6980A model
|
|
|
|
|
|
|
|
|
|
|
|
| Application |
| Default mode |
| NSB value |
| Output 1 |
| Output 1 | Maximum | Minimum |
|
|
|
| min. opening |
| opening time | setpoint | setpoint | |||
| (section 4.2) |
| (section 4.3.1) |
| (section 5.6) |
|
| ||||
|
|
|
| (section 4.3.2) |
| (section 4.3.3) | (section 4.6) | (section 4.6) | |||
|
|
|
|
|
|
|
| ||||
0 | Internal sensor | 0 | Cool | 1 | 2°F (1°C) | 0 | 0% | 0 | 80 |
|
|
1 | Room | 1 | Heat | 2 | 4°F (2°C) | 1 | 10% | 1 | 90 | Can be set | Can be set |
2 | Return |
|
| 3 | 6°F (3°C) | 2 | 20% | 2 | 100 | between 95°F | between 50°F |
3 | Supply |
|
| 4 | 8°F (4°C) | 3 | 30% | 3 | 110 | (35°C) and | (10°C) and |
|
|
|
|
|
|
|
|
|
| ’’minimum | ’’maximum |
4 | Auto changeover |
|
| 5 | 10°F (5°C) | 4 | 40% | 4 | 120 | ||
|
| setpoint + 1’’ | setpoint - 1’’ | ||||||||
5 | Limited cooling |
|
| 6 | 12°F (6°C) | 5 | 50% | 5 | 130 | ||
|
|
|
| ||||||||
|
|
|
| 7 | 14°F (7°C) |
|
| 6 | 140 | Default value | Default value |
|
|
|
|
|
|
|
|
|
| is 95°F (35°C) | is 50°F (10°C) |
|
|
|
| 8 | 16°F (8°C) |
|
| 7 | 150 | ||
|
|
|
|
|
|
|
| ||||
|
|
|
| 9 | 18°F (9°C) |
|
| 8 | 160 |
|
|
ABBREVIATIONS
NSB - Night setback (number of degrees the thermostat will be set back upon receiving a setback signal)
SSR - Solid state relay (used with fast cycling electric heaters, SSR's are a quiet alternative to electromechanical relays. They're typically included with electric duct reheat equipment)
SCR - Silicon controlled rectifier (similar to an SSR, SCR's are also quiet and capable of switching very high current. If used, they're usually included with the equipment)
N.C. - Normally closed N.O. - Normally open
TB7980B model
| Application |
| Default mode & |
| Output 2 typea |
| Output 3 type |
| Output 3 |
| NSB value |
| Output 1 | Maximum | Minimum | |
|
| Output 1 type |
|
|
| activation |
|
| min. opening | setpoint | setpoint | |||||
| (section 4.2) |
|
| (section 4.4) |
| (section 4.5) |
|
| (section 5.6) |
| ||||||
|
| (section 4.3.1) |
|
|
| (section 4.5) |
|
| (section 4.3.2) | (section 4.6) | (section 4.6) | |||||
|
|
|
|
|
|
|
|
|
|
| ||||||
0 | Internal sensor | 0 | Cool / | 0 | Not used | 0 | Not used | 0 | 100% | 1 | 2°F (1°C) | 0 | 0% |
|
| |
1 | Room | 1 | Heat / | 1 | SSR 24 VAC | 1 | SSR 24 VAC | 1 | 10% | 2 | 4°F (2°C) | 1 | 10% | Can be set | Can be set | |
2 | Return | 2 | Cool / | 2 | N.C. Valve | 2 | N.C. Valve | 2 | 20% | 3 | 6°F (3°C) | 2 | 20% | |||
between 95°F | between 50°F | |||||||||||||||
3 | Supply | 3 | Heat / | 3 | N.O. Valve | 3 | N.O. Valve | 3 | 30% | 4 | 8°F (4°C) | 3 | 30% | |||
(35°C) and | (10°C) and | |||||||||||||||
4 | Auto changeover |
|
| 4 | Mech. relay | 4 | Mech. relay | 4 | 40% | 5 | 10°F (5°C) | 4 | 40% | ’’minimum | ’’maximum | |
5 | Limited cooling |
|
| 5 | SSR | 5 | Contact | 5 | 50% | 6 | 12°F (6°C) | 5 | 50% | setpoint + 1’’ | setpoint - 1’’ | |
|
|
|
| 6 | SCR |
|
| 6 | 60% | 7 | 14°F (7°C) |
|
| Default value | Default value | |
|
|
|
| 7 | Act. |
|
| 7 | 70% | 8 | 16°F (8°C) |
|
| |||
|
|
|
|
|
|
|
| is 95°F (35°C) | is 50°F (10°C) | |||||||
|
|
|
| 8 | Act. / |
|
| 8 | 80% | 9 | 18°F (9°C) |
|
|
|
|
990%
a. If Output 2 type is set to
TB6980B model
| Application |
| Default mode |
| Output 2 typea |
| Output 3 type |
| Output 3 |
| NSB value |
| Output 1 |
| Output 1 | Maximum | Minimum |
|
|
|
|
| activation |
|
| min. opening |
| opening time | setpoint | setpoint | |||||
| (section 4.2) | (section 4.3.1) |
| (section 4.4) |
| (section 4.5) |
|
| (section 5.6) |
|
| ||||||
|
|
|
| (section 4.5) |
|
| (section 4.3.2) | (section 4.3.3) | (section 4.6) | (section 4.6) | |||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
0 | Internal sensor | 0 | Cool | 0 | Not used | 0 | Not used | 0 | 100% | 1 | 2°F (1°C) | 0 | 0% | 0 | 80 |
|
|
1 | Room | 1 | Heat | 1 | SSR 24 VAC | 1 | SSR 24 VAC | 1 | 10% | 2 | 4°F (2°C) | 1 | 10% | 1 | 90 | Can be set | Can be set |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| between | between |
2 | Return |
|
| 2 | N.C. Valve | 2 | N.C. Valve | 2 | 20% | 3 | 6°F (3°C) | 2 | 20% | 2 | 100 | ||
|
| 95°F (35°C) | 50°F (10°C) | ||||||||||||||
3 | Supply |
|
| 3 | N.O. Valve | 3 | N.O. Valve | 3 | 30% | 4 | 8°F (4°C) | 3 | 30% | 3 | 110 | ||
|
| and | and | ||||||||||||||
4 | Auto changeover |
|
| 4 | Mech. relay | 4 | Mech. relay | 4 | 40% | 5 | 10°F (5°C) | 4 | 40% | 4 | 120 | ’’minimum | ’’maximum |
5 | Limited cooling |
|
| 5 | SSR | 5 | Contact | 5 | 50% | 6 | 12°F (6°C) | 5 | 50% | 5 | 130 | setpoint + 1’’ | setpoint - 1’’ |
|
|
|
| 6 | SCR |
|
| 6 | 60% | 7 | 14°F (7°C) |
|
| 6 | 140 | Default | Default |
|
|
|
| 7 | Act. |
|
| 7 | 70% | 8 | 16°F (8°C) |
|
| 7 | 150 | ||
|
|
|
|
|
|
|
| value is 95°F | value is 50°F | ||||||||
|
|
|
| 8 | Act. / |
|
| 8 | 80% | 9 | 18°F (9°C) |
|
| 8 | 160 | (35°C) | (10°C) |
990%
a. If Output 2 type is set to
TB6980/TB7980 | 3/6 |