Honeywell manual Application Types, Output 2 models TB6980B and TB7980B, Minimum Opening

Models: TB6980 TB7980

1 6
Download 6 pages 28.33 Kb
Page 4
Image 4
4.2 Application Types

4.2 Application Types

The following table shows the different thermostat applications and their corresponding settings in the configuration menu.

Menu setting

Description

 

 

 

0

Internal

To control the ambient temperature using the internal

sensor

(built-in) sensor

 

 

 

 

 

To control the ambient temperature using the

1

Room

50014156-002 temperature sensor (the internal sensor

 

 

is not used)

 

 

 

 

 

To control the temperature at the air return using the

2

Air return

50014157-001 temperature sensor (the internal sensor

 

 

is not used)

 

 

 

 

 

To control the temperature at the fresh air supply using

3

Air supply

the 50014157-001 temperature sensor (the internal

 

 

sensor is not used)

 

 

 

 

Automatic

To control the ambient temperature using the internal

4

sensor. The 50014157-001 temperature sensor is used

 

changeover

for automatic changeover. See section 5.5.1.

 

 

 

 

 

To use the outdoor air for cooling whenever possible.

 

 

The 50014157-001 temperature sensor is used to

 

 

measure the outdoor air temperature. The internal

 

 

temperature sensor measures the room temperature

 

Limited

which is then compared with the setpoint. If the room

5

temperature is lower than the setpoint, the air intake

cooling

 

 

damper remains closed. If the room temperature is

 

 

higher than the setpoint, the latter is then compared with

 

 

the outdoor temperature. If the fresh air temperature is

 

 

lower than the setpoint by more than 5°F(3°C), the

 

 

damper opens to allow cool air in.

 

 

 

4.3 Output 1

Output 1 is used to control a damper. It controls heating when the thermostat is in heat mode or cooling when the thermostat is in cool mode.

Set the following configuration parameters:

Default mode

Output type (TB7980 models only)

Minimum opening

Opening time (TB6980 models only)

4.3.1Default Mode / Output Type

The default mode (heat/cool) is used for the following:

The default mode is the thermostat’s mode at power-up.

The default mode is the active mode when the N.O. changeover contact is open (see section 5.5.2).

When configured as a contact (see section 4.5), Output 3 controls either heating or cooling depending on whether the default mode is set to heat or cool respectively.

The following table shows the different default modes, the different output types for Output 1, and their corresponding settings in the configuration menu.

Menu setting

TB7980 models

TB6980 models

0

Cool / 0-10 V analog

Cool

(max. of 10 min. refresh)

(24 V tri-state floating)

 

1

Heat / 0-10 V analog

Heat

(max. of 10 min. refresh)

(24 V tri-state floating)

 

2

Cool / 2-10 V analog

 

(max. of 10 min. refresh)

 

 

 

3

Heat / 2-10 V analog

 

(max. of 10 min. refresh)

 

 

 

4.3.2 Minimum Opening

The minimum damper opening can be set between 0 and 50 %.

Note: It is not recommended to set the minimum damper opening to 0 % (fully closed) when a duct heater is connected to Output 2 or 3.

4.3.3 Opening time (TB6980 models only)

The damper opening time can be set between 80 and 160 seconds.

4.4 Output 2 (models TB6980B and TB7980B)

Output 2 controls heating only, regardless of the thermostat’s mode. When the thermostat is in heat mode, Output 2 is activated as soon as Output 1 reaches its full capacity. When the thermostat is in cool mode, Output 2 is activated when the measured temperature drops below the setpoint.

The following table shows the output types for Output 2 and their corresponding settings in the configuration menu.

Menu setting

 

 

Description

0

Not used

 

 

 

1

24

VAC pulsed (triac) / 1 sec. cycle

2

24

VAC pulsed (triac) / 10 min. cycle / direct action

(e.g., N.C. thermal valve)

 

3

24

VAC pulsed (triac) / 10 min. cycle / reverse action

(e.g., N.O. thermal valve)

 

4

24

VAC pulsed (triac) / 15 min. cycle (e.g., mechanical

relay such as R841)

 

5

0-10

V pulsed / 1 sec. cycle

6

0-10

V analog / 1 sec. refresh

(e.g., SCR controlled device such as a re-heater)

 

7

0-10

V analog / max. of 10 min. refresh (e.g., valve)

8

2-10

V analog / max. of 10 min. refresh (e.g., damper)

 

 

 

 

Note: If 0-4 is selected, set the SW6 switch to Triac. If 5-8 is selected, set the switch to Analog (see section 4.7)

TB6980/TB7980

4/6

Page 4
Image 4
Honeywell manual Application Types, Output 2 models TB6980B and TB7980B, Default Mode / Output Type, Minimum Opening