TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
62-0311—13 12
2 System Type 0 Heat only
1 Cool only
2 Two pipes: Heat or Cool; Manual Changeover
3 Two pipes: Heat or Cool; Seasonal Changeover
(requires optional pipe sensor)
4 Four pipes: Manual Changeover TB6575A,TB6575B and
TB6575C only
5 Four pipes: Auto Changeover TB6575A,TB6575B and
TB6575C only
6 Two pipes: Heat or Cool; with Auxiliary Heat
(requires optional pipe sensor).
Allows auxiliary heat to turn
on when pipes have cold
water
(TB6575A,TB6575B and
TB6575C only).
7 Four pipes: Manual and Auto Changeover
(Default)
TB6575A,TB6575B and
TB6575C only
2.5 Fan On/Off
Selection for Aux
Heat On
0Fan ON when Auxiliary Heat is on (Default) Enables or disables the
auto fan operation when
Auxiliary Heat is On
(TB6575A,TB6575B and
TB6575C only).
1 Fan OFF when Auxiliary Heat is on
3 Valve Output Type 0 Valve energized on call for heat or cool (Default)
1 Valve de-energized on call for heat or cool
4 Space Sensor Type 0 Onboard Sensor (Default)
1 Remote Sensor (TR21 or other 20K Ohm sensor)
5 Pipe Sensor
Only displays when
value 3 or 6 for the
System Type in IS
code #2 is selected.
0 Contact Open = Cool mode; Contact Closed = Heat
mode
•Pipe sensor will flash on
display screen if analog
input (#4) is lost.
•Pipe sensor status and
water temperature can
be checked in test mode
(see “Installer Test (IT)
Mode” on page14 for
details)
1 Contact Open = Heat mode; Contact Closed = Cool
mode
2 Contact Open = Heat mode; Contact Closed = Cool
mode (same as 1)
3 Contact Open = Cool mode; Contact Closed = Heat
mode (same as 0)
4 Analog input (Default). NTC20K, whose curve is
the same as TR21.
Only displays when system type 3 or 6 is selected.
6 Pipe Sensor
Threshold for
Cooling
50 to
72
Range is 50°F to 72°F. Default is 60°F. Changes to Cool when pipe
temperature is below
threshold.
7 Pipe Sensor
Threshold for
Heating
75 to
90
Range is 75°F to 90°F. Default is 80°F. Changes to Heat when pipe
sensor temperature is
above threshold.
8 Temperature Scale 0 Degrees Fahr enheit (°F); Default.
1 Degrees Celsius (°C).
8.5 Fan Speed at motor
start up
0Provide full power when fan motor starts –
always starts in high fan speed (Default)
High speed start up
ensures that there is
enough torque to start the
motor and eliminates and
motor locking.
1 Disable – fan will start at speed that is needed as
defined by VersaSpeed
9 Number of Fan
Speeds
1 Single Speed Fan Low speed only
2 2 Speed Fan Hi and Low speed fans only
3 3 Speed Fan (Default) Hi, Med, and Low speed fan
9.5 Fan Control Type 0 Constant and Auto (Default) When fan is in Auto, the fan
ramping algorithm,
VersaSpeed, is used
1 Auto only
Table 4. Installer Setup (IS) Codes and Options. (Continued)
IS
Code Code Description
Option
Value
Option Description (Default value shown in
Bold) Notes