VR8300A CONTINUOUS PILOT COMBINATION GAS CONTROL
Contents
Main
INSTALLATION INSTRUCTIONS
69-0668-1
VR8300A Continuous Pilot Combination Gas Control
Wrench With Hex
Type Without Hex
APPLICATION
Part Number Inlet/Outlet Pipe Size Flange
INSTALLATION
When Installing this Product
Converting Between Natural and LP Gas
Install Adapters to Gas Control
Flanges:
Use Adapters to Solve Swing Radius Problems
Choose Gas Control Location
Install Piping to Gas Control
Install Gas Control
On LP installations, use compound resistant to LP gas. Do not use Teflon tape.
Connect Pilot Gas Tubing
Connect Thermocouple
Do not overtighten
Wiring
Install Thermocouple
START -UP AND CHECKOUT
Gas Control Knob Settings
Perform Gas Leak Test
Gas Leak Test
Light Pilot Burner Flame
Adjust Pilot Burner Flame
Light Main Burner
Check and Adjust Gas Input to Main Burner
Standard-Opening and Slow-Opening Pressure Regulator
Check Safety Shutdown Performance
Dusty, wet, or corrosive environment.
Consequence of unexpected shutdown
Intermittent use
Cycling frequency
SERVICE
If Pilot Burner Flame does not Light:
If Pilot Burner Flame Goes Out when Gas Control Knob is Released:
If Main Burner does not Come on with Call For Heat:
click
Turning Off Appliance