QuickSpecs

HP ProLiant DL585

Power Specifications

Part Number

384413-001 (870W)

 

 

 

 

 

Spare Kit

192201-002 (870W)

 

 

 

 

 

Operational Input Voltage

90 to 264

 

 

 

 

 

 

Range (V rms)

 

 

 

 

 

 

 

 

Frequency Range (Nominal)

47 to 63 (50/60)

 

 

 

 

 

(Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Input Voltage (Vrms)

 

 

100

115

208

220

230

240

Max Rated Output Wattage Rating

 

800

800

800

800

800

800

Nominal Input Current (A rms)

 

 

11.7

9.9

5.2

4.9

4.7

4.5

Max Rated Input Wattage Rating (Watts)

 

1143

1111

1067

1067

1067

1053

Max. Rated VA (Volt-Amp)

 

 

1166

1134

1088

1088

1088

1074

Efficiency (%)

 

 

70

72

75

75

75

76

Power Factor

 

 

0.98

0.98

0.98

0.98

0.98

0.98

Leakage Current (mA)

 

 

.43

.50

.90

.96

1.00

1.04

Maximum Inrush Current (A peak)

 

25

25

25

25

25

25

Maximum Inrush Current duration

 

20

20

20

20

20

20

System Specifications

DL585 Fully Configured

4 processors, 32 memory modules, 4 hard drives, 8 PCI-X expansion cards, 8 hot plug fans, and 2 hot plug power supplies.

Nominal Input Voltage (Vrms)

100

115

 

208

220

230

 

240

Fully Loaded System Input Wattage (W)

954

928

 

890

890

890

 

879

Fully Loaded System Input Current (A rms)

10

8.5

 

4.4

4.1

4.0

 

3.7

Fully Loaded System Thermal (BTU- Hr)

3253

3163

 

3063

3063

3063

 

2996

Fully Loaded System VA (Volt-Amp)

1004

976

 

909

909

909

 

897

System Leakage with all power supplies loaded

.87

1.00

 

1.81

1.91

2.00

 

2.09

(mA)

 

 

 

 

 

 

 

 

System Inrush Current with all power supplies

50

50

 

50

50

50

 

50

loaded (A)

 

 

 

 

 

 

 

 

Power cord requirements

Nema 5-15P to IEC320-C19

 

Option no./Spare no: 235603-

 

 

 

 

 

 

001/237457-001

 

 

 

PDU Jumper Cord IEC320-C19 to

Option no./Spare no: 295633-

 

 

IEC320-C20

 

 

 

B21/295508-001

 

 

PDU Jumper Cord IEC320-C14 to

Option no./Spare no: 291034-

 

 

IEC320-C19

 

 

 

001/292241-001

 

 

NOTES:

*To review typical system power ratings use the Active Answers Power Calculator which is available via the online tool located at URL: http://h30099.www3.hp.com/configurator/powercalcs.asp.

To drill down to calculators:

-Click on: "ProLiant Servers"

-Click on the Server of interest. Example: DL585

-Click on: "Power Calculator" link (You may need to scroll down to see it.)

DA - 11902 Worldwide — Version 29 — May 5, 2005

Page 38

Page 38
Image 38
HP DL585 manual Power Specifications