HP ProLiant DL585
Power Specifications
Part Number |
|
|
|
|
| |||
Spare Kit |
|
|
|
|
| |||
Operational Input Voltage | 90 to 264 |
|
|
|
|
|
| |
Range (V rms) |
|
|
|
|
|
|
|
|
Frequency Range (Nominal) | 47 to 63 (50/60) |
|
|
|
|
| ||
(Hz) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Nominal Input Voltage (Vrms) |
|
| 100 | 115 | 208 | 220 | 230 | 240 |
Max Rated Output Wattage Rating |
| 800 | 800 | 800 | 800 | 800 | 800 | |
Nominal Input Current (A rms) |
|
| 11.7 | 9.9 | 5.2 | 4.9 | 4.7 | 4.5 |
Max Rated Input Wattage Rating (Watts) |
| 1143 | 1111 | 1067 | 1067 | 1067 | 1053 | |
Max. Rated VA |
|
| 1166 | 1134 | 1088 | 1088 | 1088 | 1074 |
Efficiency (%) |
|
| 70 | 72 | 75 | 75 | 75 | 76 |
Power Factor |
|
| 0.98 | 0.98 | 0.98 | 0.98 | 0.98 | 0.98 |
Leakage Current (mA) |
|
| .43 | .50 | .90 | .96 | 1.00 | 1.04 |
Maximum Inrush Current (A peak) |
| 25 | 25 | 25 | 25 | 25 | 25 | |
Maximum Inrush Current duration |
| 20 | 20 | 20 | 20 | 20 | 20 |
System Specifications
DL585 Fully Configured
4 processors, 32 memory modules, 4 hard drives, 8
Nominal Input Voltage (Vrms) | 100 | 115 |
| 208 | 220 | 230 |
| 240 |
Fully Loaded System Input Wattage (W) | 954 | 928 |
| 890 | 890 | 890 |
| 879 |
Fully Loaded System Input Current (A rms) | 10 | 8.5 |
| 4.4 | 4.1 | 4.0 |
| 3.7 |
Fully Loaded System Thermal (BTU- Hr) | 3253 | 3163 |
| 3063 | 3063 | 3063 |
| 2996 |
Fully Loaded System VA | 1004 | 976 |
| 909 | 909 | 909 |
| 897 |
System Leakage with all power supplies loaded | .87 | 1.00 |
| 1.81 | 1.91 | 2.00 |
| 2.09 |
(mA) |
|
|
|
|
|
|
|
|
System Inrush Current with all power supplies | 50 | 50 |
| 50 | 50 | 50 |
| 50 |
loaded (A) |
|
|
|
|
|
|
|
|
Power cord requirements | Nema |
| Option no./Spare no: 235603- |
| ||||
|
|
|
|
|
|
| ||
| PDU Jumper Cord | Option no./Spare no: 295633- |
| |||||
|
|
|
|
| ||||
| PDU Jumper Cord | Option no./Spare no: 291034- |
| |||||
|
|
|
|
|
|
NOTES:
*To review typical system power ratings use the Active Answers Power Calculator which is available via the online tool located at URL: http://h30099.www3.hp.com/configurator/powercalcs.asp.
To drill down to calculators:
-Click on: "ProLiant Servers"
-Click on the Server of interest. Example: DL585
-Click on: "Power Calculator" link (You may need to scroll down to see it.)
DA - 11902 Worldwide — Version 29 — May 5, 2005 | Page 38 |