Installation (cont.)
ARM STRUT
GUSSET
Corner wedges are attached via front and rear camlocks. Use a 7mm Allen wrench to turn the locks. Do not overtighten! Join the top by using a joint bracket (included in joint kit) with 3/8" bolts.
WEDGE BRACKET
Plumbing
WASTE OUTLET AND
The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture.
A
NOTE:
Follow the Hussmann’s instructions.
INSTALLING CONDENSATE DRAIN
Poorly or improperly installed condensate drains can seriously interfere with the operation of this refrigerator, and result in costly maintenance and product losses.Please follow the recommendations listed below when installing condensate drains to insure a proper installation:
1.Never use pipe for condensate drains smaller than the nominal diameter of the pipe or
2.When connecting condensate drains,the
two water seals in series in any one line. Double P- traps in series will cause a lock and prevent draining.
3.Always provide as much down hill slope (“fall”) as possible; 1/8" per foot is the preferred minimum. PVC pipe, when used, must be supported to maintain the 1/8" pitch and to prevent warping.
4.Avoid long runs of condensate drains.Long runs make it impossible to provide the “fall” necessary for good drainage.
5.Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1" is ideal.
6.Prevent condensate drains from freezing:
a.Do not install condensate drains in contact with
b.Where condensate drains are located in dead air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing. The water seal should be insulated to prevent condensation.