10% to 80% non-condensing
12º/hr C (21.6º/hr F)
67 dBA
77 dBA
12,283 Btu/hr
1.7º to 49º C (35º to 120º F)
1.7º to 45º C (35º to 113º F)
1.7º to 35º C (35º to 95º F)
15,131 Btu/hr

Operating temperature (AC and DC systems)

-200 to 6000 ft

 

4.5º to 40º C (40º to 104º F)

 

 

 

6000 to 8000 ft

8000 to 10,000 ft

4.5º to 35º C (40º to 95º F)

4.5º to 30º C (40º to 86º F)

Short term (<72 hrs) operating temp. (DC systems only)

-200 to 6000 ft

6000 to 8000 ft

8000 to 10,000 ft

Heat dissipation (maximum)

CEC cab. (AC systems)

Expansion cab. (AC systems) 15,131 Btu/hr

CEC cab. (DC systems)

Expansion cab. (DC systems) 12,283 Btu/hr

Relative humidity

Max. rate of temp. change

Acoustical noise (per cabinet)

Fans at normal speed

Fans at full speed

5.3 Electrical (AC Cabinets)

AC service requirements

 

Two 30A, single-phase AC inputs (1 active, 1 standby)

 

 

 

AC input voltage range

 

 

 

Nominal

 

200 to 240 V AC

 

 

 

Absolute

 

180 to 264 V AC

 

 

 

AC input frequency range

 

47 to 63 Hz

 

 

 

Efficiency (min.)

 

82%

 

 

 

Power factor

 

>.99 (>10% load)

 

 

 

AC input power (max.)

 

4.44 KVA

 

 

 

Input current (@ 3600 W of power delivered to load)