IBM x3759 M4, 88Y7429 manual Physical and electrical specifications

Models: 88Y7429 x3759 M4

1 44
Download 44 pages 32.62 Kb
Page 26
Image 26

Physical and electrical specifications

Dimensions and weight:

Width: 446 mm (17.5 in.)

Depth: 734 mm (28.9 in.)

Height: 87 mm (3.4 in.)

Approximate weight, fully configured: 31.1 kg (68.5 lb.)

Supported environment:

Air temperature:

5 - 40 °C (41 - 104 °F) at 0 - 3048 m (10,000 ft); ASHRAE A3 compliant

Humidity: 8% - 80%

Electrical:

100 - 127 (nominal) V AC, 50 Hz or 60 Hz, and System 20 A (10 A per power supply)

200 - 208 (nominal) V AC, 50 Hz or 60 Hz, and System 10 A

200 - 240 (nominal) V AC, 50 Hz or 60 Hz, and System 9 A

Minimum configuration: 0.20 kVA (one power supply)

Minimum configuration: 0.26 kVA (two power supplies)

Typical configuration: 1.12 kVA (two power supplies)

Maximum configuration: 2.16 kVA (two power supplies)

BTU output:

Minimum configuration: 648 BTU/hr (190 watts)

Maximum configuration: 7,336 BTU/hr (2150 watts)

Noise level:

Idle: 6.5 bels

Operating: 6.6 bels

IBM System x3750 M4

26

Page 26
Image 26