INSTALLATION

INSTALLATION

13 FRONT AND BOTTOM PANEL REMOVAL

3

1.

To remove the front panel remove the 2 screws from the

 

 

bottom panel.

 

2.

Lift the panel up and off the top pegs.

1

3.

To remove the bottom panel remove the 2 screws.

 

4.

Pull the RH side of the panel down. Slide it to the right

 

 

and withdraw.

 

14 DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED

IMPORTANT. The boiler MUST be installed in a vertical position.

FLUE KITS

Pack B - supplied as standard.

Finishing Kit - supplied as an optional extra.

Pack D - optional extension kit for side flue or rear flue outlet. Refer to 'Flue Extension Ducts'

Dimension X - Wall thickness.

Dimension L - Wall thickness plus boiler spacing. Dimension S - Stand-off frame depth = 33mm.

REAR FLUE

Note. MAXIMUM FLUE LENGTHS:

160 + S = 193mm

160 mm

HORIZONTAL FLUE - 6M

 

 

 

ROOF FLUE KIT - 7.5M

 

 

POWERED VERTICAL FLUE KIT - 5m primary and 17m secondary is a typical maximum

 

length. For alternative details refer to Powered Vertical

 

Instructions.

 

 

90O ELBOW KIT 60/100 (EQUIVALENT FLUE LENGTH RESISTANCE = 1M)

 

 

45O ELBOW KIT 60/100 (EQUIVALENT FLUE LENGTH RESISTANCE = 0.6M)

 

 

60/60 TWIN FLUE KIT - 18M TOTAL AIR PLUS FLUE DUCT - Ref Graph within Kit Instructions

 

80/80 TWIN FLUE KIT - 60M TOTAL AIR PLUS FLUE DUCT - Ref Graph within Kit Instructions

nm8943

MINIMUM HORIZONTAL FLUE LENGTHS - TELESCOPIC TERMINAL = 370MM

 

(Centre Line of turret to outside of wall terminal) - ONE PIECE TERMINAL = 285MM

 

 

 

Notes.

 

 

1. When extension ‘D’ packs are used the flue duct MUST be inclined at 1.5

Wall Thickness X

 

degrees to the horizontal to allow condensate to drain back into the boiler

 

 

and out through the condensate drain.

 

 

2.If the telescopic ‘B’ pack or horizontal flue terminal (600 long) only are used, they may be mounted horizontally. The 1.5 degrees is taken care of by the inclination of the flue within the air pipe

3.If the boiler is to be installed with downward piping routed behind the boiler

then the optional stand-off kit should be used. Care must be taken when

 

 

 

 

 

 

 

 

 

 

 

 

 

SIDE FLUE

cutting the ducts and marking the wall to suit this condition.

 

 

 

 

 

 

 

Wall Thickness X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Flue length dimension

Flue

 

195mm

 

195mm

 

 

 

 

 

 

 

 

 

 

 

 

(measuring from CL of turret to outside wall)

 

 

 

 

 

 

 

 

 

 

Rear flue

Side flue

Extra packs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dim. X+160

dim. L+195

required

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 595 mm

Up to 595 mm

none

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 1545 mm

Up to 1545 mm

Pack D - 1 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 2495 mm

Up to 2495 mm

Pack D - 2 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 3445 mm

Up to 3445 mm

Pack D - 3 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Side flue length L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 4395 mm

Up to 4395 mm

Pack D - 4 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 5345 mm

Up to 5345 mm

Pack D - 5 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 6000 mm

Up to 6000 mm

Pack D - 6 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

icos - Installation & Servicing

Page 16
Image 16
IDEAL INDUSTRIES HE24 Installation Front and Bottom Panel Removal, Determining the Flue Length and Flue Packs Required

HE12, HE15, HE18, HE24 specifications

The IDEAL INDUSTRIES HE series, comprising the HE24, HE18, HE15, and HE12 models, represents a significant advancement in the field of electrical testing and measurement tools. These versatile testers stand out in professional environments for their high accuracy, user-friendly interfaces, and advanced features designed to enhance efficiency and reliability in electrical inspections.

The HE24 is the flagship model, boasting an extensive range of functionalities. It includes advanced digital multimeter capabilities, allowing for precise measurements of voltage, current, and resistance. Its True RMS feature ensures accurate readings, even with non-linear loads. The HE24 also incorporates advanced connectivity options, including Bluetooth technology, enabling users to transfer data wirelessly to smartphones or tablets for further analysis. The large, backlit display enhances visibility in various lighting conditions, making it an ideal tool for both indoor and outdoor use.

The HE18 model, while slightly more streamlined than the HE24, still offers robust capabilities. It features multiple testing modes, including continuity and diode testing, catering to a wide range of electrical tasks. The HE18 also utilizes a user-friendly interface, allowing technicians to navigate easily through various functions. Equipped with a protective rubber housing, this model is durable and built to withstand the rigors of frequent use on job sites.

The HE15 and HE12 models represent the compact, entry-level offerings in the HE series. Designed for the budget-conscious user, these models retain essential functionalities such as basic voltage and current measuring capabilities while prioritizing ease of use. The HE15 includes a simple LED indicator to signal when measurements are being taken, promoting straightforward operation. Additionally, the HE12 features a lightweight design, making it the perfect tool for on-the-go technicians.

All models in the IDEAL INDUSTRIES HE series are engineered with safety in mind, adhering to stringent international testing standards. They provide superior insulation resistance and a high degree of accuracy, mitigating the risks associated with electrical work. Furthermore, their IP-rated enclosures ensure protection against dust and moisture, enhancing longevity.

In conclusion, the IDEAL INDUSTRIES HE24, HE18, HE15, and HE12 series represent a comprehensive range of electrical testing tools that cater to professionals' varied needs. With their combination of advanced features, user-friendly designs, and safety compliance, these models are excellent choices for any electrical technician aiming for accuracy and efficiency in their work.