EPS1U Power Supply Design Guide, V1.1
4.3Airflow Requirements
STATUS
Recommended
The power supply shall have a
4.4Temperature Requirements
STATUS
Recommended
The power supply shall operate within all specified limits over the Top temperature range. The average air temperature difference (ΔTps ) from the inlet to the outlet of the power supply shall not exceed the values shown in Table 2. All airflow shall pass through the power supply and not over the exterior surfaces of the power supply.
Table 2: Thermal Requirements
Item |
| Description | MIN | MAX | Units |
Top | Operating temperature range. | 0 | 45 | °C | |
|
|
|
|
| |
ΔTps | Temperature rise from inlet air to outlet air of power supply. |
| 15 |
| |
| 125 | W output power, 10 CFM, Sea level, 25 °C inlet air. |
| °C | |
| 125 | W output power, 6 CFM, Sea level, 25 °C inlet air. |
| 25 | °C |
| Temperature rise from inlet air to outlet air of power supply. |
|
|
| |
| 250 | W output power, 10 CFM, Sea level, 25 °C inlet air. |
| 20 | °C |
| 250 | W output power, 6 CFM, Sea level, 25 °C inlet air. |
| 30 | °C |
| 350 | W output power, 10 CFM, Sea level, 25 °C inlet air. |
| 30 | °C |
| 350 | W output power, 6 CFM, Sea level, 25 °C inlet air. |
| 40 | °C |
70 | °C |
The power supply must meet UL enclosure requirements for temperature rise limits. All sides of the power supply, with exception to the air exhaust side, must be classified as “Handle, knobs, grips, etc. held for short periods of time only”.