START HERE This Quick Start Reference provides information on setting up your instrument for basic operation.

The latest complete Communication and Operational Manual as well as free Software and ActiveX Controls are available at www.omega.com/specs/iseries or

on the CD-ROM enclosed with your shipment.

SAFETY CONSIDERATION

This device is marked with the international Caution symbol.

The instrument is a panel mount device protected in accordance with EN61010-1:2001. Remember that the unit has no power-on switch. Building installation should include a switch or circuit-breaker that must be compliant to IEC 947-1 and 947-3.

SAFETY:

Do not exceed voltage rating on the label located on the top of the instrument housing.

Always disconnect power before changing signal and power connections.

Do not use this instrument on a work bench without its case for safety reasons.

Do not operate this instrument in flammable or explosive atmospheres.

Do not expose this instrument to rain or moisture.

EMC:

Whenever EMC is an issue, always use shielded cables.

Never run signal and power wires in the same conduit.

Use signal wire connections with twisted-pair cables.

Install Ferrite Bead(s) on signal wire close to the instrument if EMC problems persist.

MOUNTING

Panel Mounting Instruction:

1.Using the dimensions from the panel cutout diagram shown above, cut an opening in the panel.

2.Insert the unit into the opening from the front of the panel, so the gasket seals between the bezel and the front of the panel.

3.Slide the retainer over the rear of the case and tighten against the backside of the mounting panel.

Disassembly Instruction:

If necessary, the unit may be removed from the panel and opened.

Warning: Disconnect all ac power from the unit before proceeding.

1.Make sure the AC power is disconnected.

2.Remove all wiring connections from the rear of the meter. To remove power and input connectors bend the side panel detents on the case outward to release the connectors, then pull connectors from the meter.

3.To remove meter from the case, squeeze left and right sides of the bezel to release, then pull from case.

WIRING

Wire the instrument according to the figure shown below.

Warning: Do not connect ac power to your device until you have completed all input and output connections. This device must only be installed by a specially trained electrician with corresponding qualifications. Failure to follow all instructions and warnings may result in injury!

If instrument has the communication option, the internal excitation is not available. Use external excitation to power your transducer.

Connect the main power connections in the figure shown below.

1 2 3 4 5 6 7 8

FUSE

Connector

Output Type

For 115Vac

For 230Vac

DC

FUSE 1

Output 1

Relay

3 A(T)

3 A(T)

-

FUSE 2

Output 2

Relay

3 A(T)

3 A(T)

-

FUSE 3

Power

N/A

100 mA(T)

100 mA(T)

100 mA(T)

FUSE 4

Power

N/A

N/A

N/A

400 mA(T)

CONFIGURATION

Button Functions in Configuration Mode

To enter the Menu, the user must first press a

button.

a• Use this button to advance/navigate to the next

MENU

menu item. The user can navigate through all the

top level menus by pressing a.

 

While a parameter is being modified, press a to escape without saving the parameter.

Press the up b button to scroll through “flashing” selections. When a numerical value is displayed press this key to increase value of a parameter

bthat is currently being modified.

PK/GRS

Holding the b button down for approximately

(UP)

3 seconds will speed up the rate at which the

 

setpoint value is incremented.

In the Run Mode pressing b causes the display to flash the PEAK or GROSS value – press again to return to the Run Mode.

Press the down c button to go back to a previous Top Level Menu item.

Press this button twice to reset the controller to the Run Mode.

When a numerical value is flashing (except setpoint value) press c to scroll digits from left to

cright allowing the user to select the desired digit to

TARE

modify.

• When a setpoint value is displayed press c to

(DOWN)

 

decrease value of a setpoint that is currently being

 

modified. Holding the c button down for

 

approximately 3 seconds will speed up the rate at

 

which the setpoint value is decremented.

In the Run Mode pressing c causes the display to flash TARE value to tare your reading (zeroing).

Press the enter d button to access the submenus from a Top Level Menu item.

Press d to store a submenu selection or after entering a value — the display will flash a STRD

dmessage to confirm your selection.

ENTER • To reset flashing PEAK or GROSS press d.

In the Run Mode, press d twice to enable Standby Mode with flashing STBY.

Reset: Except for Alarms, modifying any settings of the menu configuration will reset the controller prior to resuming Run Mode.

DISPLAY ABBREVIATIONS

SP1

Set Point 1 Value

SP2

Set Point 2 Value

CNFG

Configuration Menu

INPt

Input Type (Range)

INPt

Input Type (range)

0 - 0.1

100 mV Input Voltage

0 - 1.0

1 V Input Voltage

0 - 10

10 V Input Voltage

0 - 20

20 mA Input Current

 

 

Rtio

Ratiometric Operation

RESO

Display Resolution

bUtN

Button Peak/Gross

PEAk

Peak Value

GROS

Gross Value

 

 

RdG

Reading Configuration

 

 

dEC

Decimal Point

F.FFF

Decimal Point

 

 

..FFFF

Position

LOAd

Input Load

EnbL

Scaling with Known

 

 

 

Loads (Actual Value)

DSbL

Scaling without Known

L.PNt

Linearization Points

 

Loads (Calculated Value)

 

 

0002...

Number of Linearization

FLtR

Filter Constant

...0010

Points

 

 

0001..

Filter Constant Value

IN.Rd

Input/Reading Scale

..0128

 

 

and Offset Menu

IN 1

Input 1

Rd 1

Reading 1

IN 2

Input 2

Rd 2

Reading 2

ANLG

Analog Output

CURR

Current Output

VoLt

Voltage Output

Rd 1

Reading 1

Out.1

Output 1

Rd 2

Reading 2

Out.2

Output 2

 

 

ALR1

Alarm 1 Menu

AbSo

Absolute Mode

_dEV

Deviation Mode

LtcH

Latched Mode

UNLt

Unlatched Mode

Ct.CL

Contact Closure

N.o.

Normally Open

N.c.

Normally Closed

ActV

Active Type

AboV

Active Above

bELo

Active Below

Hi.Lo

Above High/Below

 

 

 

Low

bANd

Above or Below Band

A.P.oN

Alarm Enable/Disable

 

 

 

at Power On

ALR.L

Alarm Low Value

ALR.H

Alarm High Value

ALR.2

Alarm 2 Menu

 

 

LOOP

Loop Break Menu

b.tIM

Loop Break Time

R.AdJ

Reading Adjust

SP.dN

Set Point Deviation

OUt1

Output 1 Menu

SELF

Manual Control

ººLO

Percent Low

ººHI

Percent High

Control Type

On/Off Control

CtRL

ON.OF

4 -20

Amplitude Control

PId

PID Control

ActN

Action Type

RVRS

Reverse Action

dRct

Direct Action

ANt1

Anti Integral

AUto

Auto PID

A.tUN

Auto Tune PID

StRt

Start Auto Tune PID

PRoP

Proportional Band

RESt

Reset Setup

RAtE

Rate Setup

CYCL

Cycle Time

dPNG

Damping Factor

dEAd

Dead Band

 

 

OUt2

Output 2 Menu

 

 

RAMP

Ramp Time

SOAk

Soak Time

Id

ID Code Menu

CH.Id

Change ID Code

FULL

Full ID

SP.Id

Set Point ID

COMM

Communication Option*

NONE

Communication is

 

 

 

Not Installed

COLR

Display Color Selection

N.CLR

Normal Color Display

1.CLR

Alarm 1 Color Display

2.CLR

Alarm 2 Color

 

 

 

Display

REd

Display Color is Red

AMbR

Display Color is

 

 

 

Amber

GRN

Display Color is Green

 

 

dSbL

Disable

ENbL

Enable

ERRO

Error

+ OL

Input (+) Overload

 

 

 

 

* For abbreviations of Communication Option see Communication Manual.

Page 2
Image 2
Iomega CNIS32 Safety Consideration, Emc, Mounting, Wiring, Configuration, Display Abbreviations SP1, SP2, Cnfg, Reso, Gros