Johnson Controls 340968-XIM-A-0108 Physical Data, Electrical Data, See FILTERS on page

Models: 340968-XIM-A-0108

1 24
Download 24 pages 36.53 Kb
Page 10
Image 10
TABLE 7: PHYSICAL DATA

340968-XIM-A-0108

TABLE 7: PHYSICAL DATA

 

MODEL

 

 

 

DNA

 

 

 

 

018

024

030

036

042

048

060

 

 

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x W. in.)

10 x 8

10 x 8

10 x 8

11 x 10

11 x 10

12 x 11

12 x 11

BLOWER

FAN MOTOR HP (3 Speed)

1/2

1/2

1/2

3/4

3/4

1

1

 

 

 

 

 

 

 

 

 

EVAPORATOR

ROWS DEEP

2

2

2

2

3

3

3

FINS PER INCH

14

13

13

15

13

13

13

COIL

FACE AREA (Sq. Ft.)

2.25

3.5

3.5

3.5

3.5

4.5

4.5

 

 

 

 

 

 

 

 

 

 

CONDENSER

PROPELLER DIA. (in.)

22

22

22

22

22

22

22

FAN MOTOR HP

1/4

1/4

1/4

1/4

1/4

1/4

1/4

FAN

NOM. CFM TOTAL

1,800

2,200

2,400

2,400

2,400

3,000

3,000

 

 

 

 

 

 

 

 

 

 

CONDENSER

ROWS DEEP

1

1

1

1

1

1

1

FINS PER INCH

13

13

16

20

20

20

20

COIL

FACE AREA (Sq. Ft.)

8.3

8.3

11.7

11.7

11.7

14.8

14.8

 

 

 

 

 

 

 

 

 

 

CHARGE

REFRIGERANT 22 (lbs./oz.)

3 / 2

3 / 16

4 / 12

4 / 3

4 / 9

6 / 0

5 / 4

 

 

 

 

 

 

 

 

 

FILTER1

FACE AREA (Sq. Ft.) Size (Nominal)

2.6/20x20

2.6/20x20

2.6/20x20

2.6/20x20

2.6/20x20

3.3/20x12

3.3/20x12

FURNACE

NATURAL GAS BURNER ORIFICE NO. (Drill Size)

43

43

43

43

43

40

40

PROPANE BURNER ORIFICE NO. (Drill Size)

55

55

55

55

55

53

53

SECTION

GAS CONNECTION SIZE

1/2 NPTI

1/2 NPTI

1/2 NPTI

1/2 NPTI

1/2 NPTI

1/2 NPTI

1/2 NPTI

 

 

 

 

 

 

 

 

 

 

COMPRESSOR

HERMETICALLY SEALED

R

R

R

R

R

S

S

TYPE

(R = RECIPROCATING, S = SCROLL)

 

 

 

 

 

 

 

1.See FILTERS on page 5.

TABLE 8: ELECTRICAL DATA

 

 

VOLTAGE

COMPRESSOR

COND.

SUPPLY

 

MAX.

MAX.

 

 

MODEL

POWER

LIMITATIONS1

AIR

MINIMUM

HACR

UNIT

TRANSFORMER

 

 

FAN

FUSE

DNA

SUPPLY

 

 

 

 

MOTOR,

BLOWER

CIRCUIT

SIZE,

BREAKER

POWER

SIZE (VA)

MIN.

MAX.

RLA

LRA

 

 

FLA

MOTOR

AMPACITY

AMPS2

SIZE,

FACTOR

 

 

 

 

 

 

 

 

FLA

 

 

AMPS

 

 

018

208/230-1-60

187

253

9.0

48.0

1.1

2.2

14.5

20

20

.96

40

024

208/230-1-60

187

253

11.5

60.0

1.1

2.2

17.7

25

25

.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

030

208/230-1-60

187

253

14.7

73.0

1.1

2.2

21.7

30

30

.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

036

208/230-1-60

187

253

17.3

94.0

1.1

3.5

26.2

35

35

.96

40

042

208/230-1-60

187

253

15.4

86.0

1.1

3.5

23.9

30

30

.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

048

208/230-1-60

187

253

24.4

140.0

1.3

7.0

38.8

50

50

.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

060

208/230-1-60

187

253

28.9

175.0

1.3

7.0

44.4

60

60

.96

40

1.Utilization range “A” in accordance with ARI Standard 110.

2.Dual element, time delay type.

10

Johnson Controls Unitary Products

Page 10
Image 10
Johnson Controls 340968-XIM-A-0108 Physical Data, Electrical Data, See FILTERS on page, Dual element, time delay type