ACCESSORY KIT INSTALLATION MANUAL
LOW AMBIENT PRESSURE KIT MODEL 2LA06700224 & 2LA06700424
FOR MODELS: SPLIT SYSTEM AIR CONDITIONERS AND HEAT PUMPS
GENERAL INFORMATION
The low ambient pressure switch kit (2LA06700224) for
The supplied relay has a
INSTALLATION
Make sure the electric power is
1.Disconnect power to the unit.
2.Remove the control access panel.
3.Locate the liquid line base valve and remove the cap off the schrader valve.
4.Attach the tee fitting and pressure switch to the liquid line base valve , as shown in Figure 1.
ambient kit in the order to disable low ambient fan cycling in the heat mode.
When applying this kit, a TXV must be used on the indoor coil- and a crankcase heater should be added. This will guard against liquid migration and hard starts which could lead to pre- mature failure of the compressor.
PRE-INSTALLATION INFORMATION AND INSTRUCTIONS
TO LOW VOLTAGE BOX
PRESSURE SWITCH
FLARE
FITTING
VALVE
CAP
TEE FITTING ASSEMBLY
Improper installation, adjustment service, or mainte- nance can cause injury or property damage; there- fore, only a qualified installer or qualified service personnel should perform the conversion.
1.With this kit, only use motors that are single phase, perma- nent split, capacitor type or shaded pole motors.
2.Line Voltage Range: 120 to 600 Volts AC.
3.Wiring must comply with all local and national electric codes.
4.Crankcase heater should be applied in conjunction with this kit.
INSPECTION
The following list details the parts included in this kit. Inspect the kit to ensure that all the parts are included.
TABLE 1: Source 1
ITEM | QTY. | PART NO. | DESCRIPTION |
1 | 1 | 513033 | Pressure Switch |
2 | 1 | Relay | |
3 | 2 | — | Black Wire |
4 | 1 | — | Black Wire |
5 | 2 | Screw | |
6 | 2 | — | Wire Tie |
7 | 1 | 6666 | Tee Fitting |
8 | 1 | Line Splice Connection |
FLARE FITTING
WITH DEPRESSOR
BRASS REFRIGERANT
VALVE (Liquid)
FIGURE 1: Pressure Switch Assembly
5.Tighten all connections using a 9/16” wrench. Check the connections between the switch and schrader valve for leaks.
6.Route the pressure switch wires through the grommet located on the bottom of the control box. Secure the wires away from hot refrigerant lines with a wire tie.
7.Secure the relay with #10 screws included in the kit. Use the relay to mark and drill two (9/64 inch) holes so that the relay is 1/2 inch away from high voltage wiring and compo- nents.
8.To wire the low ambient pressure kit:
a.For 1 and 3 phase AC, use Figure 2.
b.For 1 and 3 phase HP, use Figure 3*.
*To connect wires to “O” and “C” in the low voltage box, cut off wire connections from the additional black wires provided in kit and strip insulation from wire. Use existing wire nuts to connect into “O” and “C” junction.
9.Replace the control access panel and restore power to the unit.
10.With the unit running in the cooling mode, make sure the outdoor fan operates properly and replace all schrader valve caps.
Johnson Controls Unitary Products |