Johnson Controls TCGF24 dimensions Physical and Electrical Data, request, Model, Unit, Inches

Models: TCGF24

1 4
Download 4 pages 50.83 Kb
Page 1
Image 1
TABULAR DATA SHEET

TABULAR DATA SHEET

Outdoor Split System Air Conditioner 2 Thru 5 Tons

MODELS: TCGF24* THRU 60 14.5 SEER – R-410A, 1 PHASE

Physical and Electrical Data

MODEL

 

TCGF24S41S1

TCGF30S41S1

TCGF36S41S1

TCGF42S41S1

TCGF48S41S1

TCGF60S41S1

Unit Supply Voltage

 

 

208-230V,

1φ, 60Hz

 

 

Normal Voltage Range 1

 

 

187 to 252

 

 

Minimum Circuit Ampacity

16.8

18.4

19.1

23.9

27.9

35.9

Max. Overcurrent Device Amps 2

25

30

30

40

45

60

Min. Overcurrent Device Amps 3

20

20

20

25

30

40

Compressor Type

 

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Compressor

Rated Load

12.8

14.1

14.1

17.9

21.1

27.5

Amps

Locked Rotor

58

73

77

112

115

135

Crankcase Heater

 

No

No

No

No

No

No

Fan Motor Amps

Rated Load

.8

.8

1.5

1.5

1.5

1.5

Fan Diameter Inches

22

22

22

24

24

24

 

Rated HP

1/8

1/8

1/4

1/4

1/4

1/4

Fan Motor

Nominal RPM

1075

1075

850

850

850

850

 

Nominal CFM

2750

2800

3200

3600

3600

3700

 

Face Area Sq. Ft.

13.1

17.4

17.4

20.0

21.4

24.0

Coil

Rows Deep

1

1

1

1

1

1

 

Fin / Inches

23

23

23

23

23

23

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

7/8

7/8

1 1/8

Unit Charge (Lbs. - Oz.) 4

3 - 2

3 - 7

3 - 10

4 - 4

4 - 9

5 - 9

Charge Per Foot, Oz.

0.62

0.62

0.62

0.67

0.67

0.75

Operating Weight Lbs.

128

130

145

172

180

199

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

 

 

 

 

All dimensions are in inches. They are subject to change

 

 

 

 

without notice. Certified dimensions will be provided upon

 

 

C

 

request.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

Dimensions

 

Refrigerant Connection

 

 

 

 

 

 

 

 

(Inches)

 

Service Valve Size

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

 

B

 

C

Liquid

Vapor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

 

28

 

29

 

29

 

 

A

 

 

 

30

 

36

 

29

 

29

 

3/4”

 

 

 

 

 

36

 

36

 

29

 

29

3/8”

 

 

 

 

 

 

 

 

 

 

 

42

 

34

 

33.6

 

33.6

7/8”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

 

36

 

33.6

 

33.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

40

 

33.6

 

33.6

 

7/8”2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

1.

Including Fan Guard.

 

 

 

 

 

 

 

2. Adapter fitting required for 1-1/8” line set.

 

 

 

 

 

 

 

Johnson Controls Unitary Products

362564-UTD-B-0708

Page 1
Image 1